WIKA DPT-10 User Manual
Page 47
Unit of measurement
Density
0001000
kg/dm³
6
Enter the requested density value with [->] and [+], confirm with
[OK]
and move to position correction with [->].
The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->]
(e.g. °F).
à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
The position correction compensates the influence of the installation
position of the instrument on the measured value. In this menu item,
the offset value as well as the current measured value are displayed.
Proceed as follows:
1
Activate in the menu item "Position correction" the selection with
[OK]
.
Position correction
Offset
DP
=
0.0000 bar
0.0035 bar
2
Select with [->], e.g. to accept the actual measured value
0.0035 bar.
Position correction
Accept current measured
value?
▶
Accept
Edit
3
Confirm with [OK].
Position correction
Offset
DP
=
-0.0035 bar
0.0000 bar
4
Move to min. (zero) adjustment with [->].
The current measured value was corrected to 0, the corrective value is
available in the display as offset value with sign reversal.
Position correction
Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA
47
6 Adjustment with the indicating and adjustment module
37245
-
EN
-100120