Table 8: Typical Unit Operating Pressures and Temperatures
Table 9: Water Temperature Change Through Heat Exchanger
Unit Operating Conditions
Water Flow, gpm [l/m]
Rise, Cooling
°F, [°C]
Drop, Heating
°F, [°C]
For Closed Loop: Ground Source or
Closed Loop Systems at 3 gpm per ton
[3.9l/m per kw]
9-12
4-11
For Open Loop: Ground Water Systems at
1.5 gpm per ton [2.0l/m per kw]
18-23
7-20
Entering
Water
Temp F
Voltage
Cooling
Heating
Suction Pres-
sure PSIG
Dis-
charge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp
Rise F
Air
Temp
Drop
F DB
Suction
Pressure
PSIG
Dis-
charge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp
Drop F
Air
Temp
Rise F
DB
30
1.5
60-69
297-321
9-15
6-14
7-10
18-23
2.3
63-72
301-325
9-15
6-14
5-8
19-23
3.0
67-76
305-329
9-15
6-14
4-6
21-24
50
1.5
128-130
227-249
10-14
12-20
21-23
21-26
88-98
329-360
8-14
5-17
10-13
26-28
2.3
128-130
213-234
11-17
10-18
15-17
21-26
93-103
334-365
8-14
5-17
7-11
27-30
3.0
124-131
199-219
12-24
8-16
9-11
21-26
97-108
339-371
8-14
5-17
5-8
27-31
70
1.5
131-136
311-334
7-12
11-20
20-22
20-25
117-129
359-394
9-14
7-18
13-19
31-34
2.3
130-135
297-323
8-11
10-16
14-17
20-25
126-136
369-409
9-14
7-18
10-15
32-36
3.0
130-138
283-318
11-14
7-13
9-12
20-25
133-145
378-425
9-14
7-18
7-10
34-37
90
1.5
134-140
388-428
7-10
10-15
18-21
20-25
158-169
397-441
11-17
3-17
17-20
37-41
2.3
133-139
370-406
8-10
9-13
13-17
20-25
167-179
407-452
11-17
3-17
13-16
38-42
3.0
131-138
353-383
8-10
7-12
9-12
20-25
176-190
418-492
11-17
3-17
9-11
39-42
110
1.5
139-152
485-520
5-10
9-19
18-20
19-24
2.3
138-146
469-497
6-10
7-17
13-16
19-24
3.0
137-144
449-475
7-10
6-14
9-12
19-24
*Based on Nominal 400 cfm per ton airflow and 70°F EAT htg and 80/67°F EAT cooling
**Cooling air and water numbers can vary greatly with changes in humidity
Subcooling is based upon the head pressure at compressor service port