Blower performance, Hkv 096 blower performance, Table continued from previous page – Comfort-Aire HKV300A User Manual
Page 29: Hkv series, Installation, operation & maintenance, Heat controller, llc
![background image](/manuals/463440/29/background.png)
Installation, Operation & Maintenance
HKV SERIES
Heat Controller, LLC
28
Blower Performance
HKV 096 Blower Performance
3800
BHP
0.84
0.89
0.94
1.04
1.13
1.19
1.24
1.34
1.43
1.49
1.54
1.64
1.73
1.79
1.84
1.94
3800
Sheave/Mtr
B
A
A
A
A
A
A
A
C
C
E
E
E
E
E
E
3800
RPM
515
549
580
611
640
667
696
721
749
773
798
823
847
872
894
918
3800
Turns Open
2
5.5
4.5
4
3.5
2.5
1.5
1.5
5.5
5
4
3.5
3
2.5
2
1
3900
BHP
0.89
0.94
1.04
1.09
1.14
1.24
1.34
1.39
1.44
1.54
1.64
1.69
1.74
1.84
1.94
3900
Sheave/Mtr
A
A
A
A
A
A
A
A
C
E
E
E
E
E
E
3900
RPM
525
556
586
617
645
674
701
726
753
778
804
827
850
875
897
3900
Turns Open
6
5.5
4.5
4
3
2.5
1.5
1
5.5
5
4
3.5
2.5
2
2
4000
BHP
0.94
1.04
1.09
1.14
1.24
1.34
1.44
1.49
1.54
1.64
1.74
1.79
1.84
1.94
4000
Sheave/Mtr
A
A
A
A
A
A
A
A
E
E
E
E
E
E
4000
RPM
539
569
601
629
659
685
711
738
763
789
812
835
860
882
4000
Turns Open
5.5
5
4.5
3.5
3
2
1
1
5
4.5
3.5
3
2.5
2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Table Continued from Previous Page
All Data is Wet Coil
Airflow
(SCFM)
ESP
Airflow (cfm) at External Static Pressure (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50