Electrical Data
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in an
open position during installation.
8VHRQO\FRSSHUFRQGXFWRUVIRU¿HOGLQVWDOOHGHOHFWULFDOZLU-
ing. Unit terminals are not designed to accept other types
of conductors.
Table 4A: HKV Electrical Data Standard
WARNING!
!
!
CAUTION!
!
!
Model
Voltage
Code
Voltage
Min/Max
Voltage
Blower
Option
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
HKV084
3
208-3-60
197/254
A, B, C
1
23.2
164.0
4.0
27.2
33.0
50
3
208-3-60
197/254
D, E
1
23.2
164.0
5.0
28.2
34.0
50
4
460-3-60
414/506
A, B, C
1
11.2
75.0
2.0
13.2
16.0
25
4
460-3-60
414/506
D, E
1
11.2
75.0
2.4
13.6
16.4
25
5
575-3-60
518/633
A, B, C
1
7.9
54.0
1.4
9.3
11.3
15
5
575-3-60
518/633
D, E
1
7.9
54.0
1.9
9.8
11.8
15
HKV096
3
208-3-60
197/254
A, B, C
1
25.0
164.0
5.0
30.0
36.3
60
3
208-3-60
197/254
D, E
1
25.0
164.0
6.2
31.2
37.5
60
4
460-3-60
414/506
A, B, C
1
12.2
100.0
2.4
14.6
17.6
25
4
460-3-60
414/506
D, E
1
12.2
100.0
3.1
15.3
18.4
30
5
575-3-60
518/633
A, B, C
1
9.0
78.0
1.9
10.9
13.1
20
5
575-3-60
518/633
D, E
1
9.0
78.0
2.3
11.3
13.6
20
HKV120
3
208-3-60
197/254
A, B, C
1
30.1
225.0
6.2
36.3
43.8
70
3
208-3-60
197/254
D, E
1
30.1
225.0
9.2
39.3
46.8
70
4
460-3-60
414/506
A, B, C
1
16.7
114.0
3.1
19.8
24.0
40
4
460-3-60
414/506
D, E
1
16.7
114.0
4.3
21.0
25.2
40
5
575-3-60
518/633
A, B, C
1
12.2
80.0
2.3
14.5
17.5
25
5
575-3-60
518/633
D, E
1
12.2
80.0
3.4
15.6
18.6
30
HKV150
3
208-3-60
197/254
A, B, C
1
48.1
245.0
9.2
57.3
69.3
110
3
208-3-60
197/254
D, E
1
48.1
245.0
14.1
62.2
74.2
110
4
460-3-60
414/506
A, B, C
1
18.6
125.0
4.3
22.9
27.6
45
4
460-3-60
414/506
D, E
1
18.6
125.0
7.0
25.6
30.3
45
5
575-3-60
518/633
A, B, C
1
14.7
100.0
3.4
18.1
21.8
35
5
575-3-60
518/633
D, E
1
14.7
100.0
5.2
19.9
23.6
35
HKV168
3
208-3-60
197/254
A, B, C
2
23.2
164.0
6.2
52.6
58.4
80
3
208-3-60
197/254
D, E
2
23.2
164.0
9.2
55.6
61.4
80
4
460-3-60
414/506
A, B, C
2
11.2
75.0
3.1
25.5
28.3
35
4
460-3-60
414/506
D, E
2
11.2
75.0
4.3
26.7
29.5
40
5
575-3-60
518/633
A, B, C
2
7.9
54.0
2.3
18.1
20.1
25
5
575-3-60
518/633
D, E
2
7.9
54.0
3.4
19.2
21.2
25
HKV192
3
208-3-60
197/254
A, B, C
2
25.0
164.0
9.2
59.2
65.4
90
3
208-3-60
197/254
D, E
2
25.0
164.0
14.1
64.1
70.3
90
4
460-3-60
414/506
A, B, C
2
12.2
100.0
4.3
28.7
31.8
40
4
460-3-60
414/506
D, E
2
12.2
100.0
7.0
31.4
34.5
45
5
575-3-60
518/633
A, B, C
2
9.0
78.0
3.4
21.4
23.6
30
5
575-3-60
518/633
D, E
2
9.0
78.0
5.2
23.2
25.5
30
HKV240
3
208-3-60
197/254
A, B, C
2
30.1
225.0
14.1
74.3
81.8
110
3
208-3-60
197/254
E
2
30.1
225.0
21.7
81.9
89.4
110
4
460-3-60
414/506
A, B, C
2
16.7
114.0
7.0
40.4
44.6
60
4
460-3-60
414/506
E
2
16.7
114.0
10.0
43.4
47.6
60
5
575-3-60
518/633
A, B, C
2
12.2
80.0
5.2
29.6
32.6
40
5
575-3-60
518/633
E
2
12.2
80.0
7.7
32.1
35.1
45
HKV300
3
208-3-60
197/254
A, B, C
2
48.1
245.0
14.1
110.3
122.3
150
3
208-3-60
197/254
D, E
2
48.1
245.0
21.7
117.9
129.9
175
4
460-3-60
414/506
A, B, C
2
18.6
125.0
7.0
44.2
48.9
60
4
460-3-60
414/506
D, E
2
18.6
125.0
10.0
47.2
51.9
70
5
575-3-60
518/633
A, B, C
2
14.7
100.0
5.2
34.6
38.3
50
5
575-3-60
518/633
D, E
2
14.7
100.0
7.7
37.1
40.8
50
HACR circuit breaker in USA only
Created: 3/26/09B
All fuses Class RK-5