Installation, Operation & Maintenance

HKV SERIES

Heat Controller, LLC

35

HKV 192 Blower Performance

Table Continued from Previous Page

All Data is Wet Coil

7600

BHP

1.68

1.78

1.88

2.08

2.26

2.38

2.48

2.68

2.86

2.98

3.08

3.28

3.46

3.58

3.68

3.88

7600

Sheave/Mtr

B

B

B

A

A

A

A

A

A

A

D

E

E

E

E

E

7600

RPM

515

549

580

611

640

667

696

721

749

773

798

823

847

872

894

918

7600

Turns Open

4

3

2

6

5.5

4.5

3.5

3

2.5

2

1

3.5

3

2

1.5

1

7800

BHP

1.78

1.88

2.08

2.18

2.28

2.48

2.68

2.78

2.88

3.08

3.28

3.38

3.48

3.68

3.88

4.08

7800

Sheave/Mtr

B

B

B

A

A

A

A

A

A

D

D

E

E

E

E

E

7800

RPM

525

556

586

617

645

674

701

726

753

778

804

827

850

875

897

921

7800

Turns Open

4

2.5

2

5.5

5

4

3.5

3

2.5

1.5

1

3.5

2.5

2

1.5

1

8000

BHP

1.88

2.08

2.18

2.28

2.48

2.68

2.88

2.98

3.08

3.28

3.48

3.58

3.68

3.88

4.08

4.28

8000

Sheave/Mtr

B

B

B

A

A

A

A

A

D

D

E

E

E

E

E

E

8000

RPM

539

569

601

629

659

685

711

738

763

789

812

835

860

882

906

927

8000

Turns Open

3

2.5

1.5

5.5

4.5

4

3

2.5

2

1.5

4

3

2.5

2

1.5

1

A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

Blower Performance