Blower performance, Hkv series, Installation, operation & maintenance – Comfort-Aire HKV300A User Manual
Page 36: Heat controller, llc
Installation, Operation & Maintenance
HKV SERIES
Heat Controller, LLC
35
HKV 192 Blower Performance
Table Continued from Previous Page
All Data is Wet Coil
7600
BHP
1.68
1.78
1.88
2.08
2.26
2.38
2.48
2.68
2.86
2.98
3.08
3.28
3.46
3.58
3.68
3.88
7600
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
D
E
E
E
E
E
7600
RPM
515
549
580
611
640
667
696
721
749
773
798
823
847
872
894
918
7600
Turns Open
4
3
2
6
5.5
4.5
3.5
3
2.5
2
1
3.5
3
2
1.5
1
7800
BHP
1.78
1.88
2.08
2.18
2.28
2.48
2.68
2.78
2.88
3.08
3.28
3.38
3.48
3.68
3.88
4.08
7800
Sheave/Mtr
B
B
B
A
A
A
A
A
A
D
D
E
E
E
E
E
7800
RPM
525
556
586
617
645
674
701
726
753
778
804
827
850
875
897
921
7800
Turns Open
4
2.5
2
5.5
5
4
3.5
3
2.5
1.5
1
3.5
2.5
2
1.5
1
8000
BHP
1.88
2.08
2.18
2.28
2.48
2.68
2.88
2.98
3.08
3.28
3.48
3.58
3.68
3.88
4.08
4.28
8000
Sheave/Mtr
B
B
B
A
A
A
A
A
D
D
E
E
E
E
E
E
8000
RPM
539
569
601
629
659
685
711
738
763
789
812
835
860
882
906
927
8000
Turns Open
3
2.5
1.5
5.5
4.5
4
3
2.5
2
1.5
4
3
2.5
2
1.5
1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Blower Performance