Unit Commissioning & Operating Conditions
BUILDING COMMISSIONING
ALL HKV MODELS
Cooling °F [°C]
Heating °F [°C]
AMBIENT MIN - MAX DB
45-110 [7-43]
40-85 [4.5-29]
RETURN AIR MIN DB/WB
50/45 [10/7]
40 [4.5]
RETURN AIR MAX DB/WB
110/83 [43/28]
85 [29]
STANDARD UNIT ENTERING
WATER MIN* - MAX
40-120 [4.5-49]
60-90 [16-43]
EXTENDED RANGE UNIT** EN-
TERING WATER MIN* - MAX
30-120 [-1-49]
20-90 [-6.7-43]
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumperclipped.
UNIT OPERATING LIMITS
All HKV Models
Cooling °F [°C]
Heating °F [°C]
AMBIENT MIN - MAX DB
50-100 [10-38]
50-85 [10-29]
RETURN AIR MIN DB/WB
65/60 [18/15.5]
60 [16]
RETURN AIR MAX DB/WB
95/75 [35/24]
80 [27]
STANDARD UNIT ENTERING
WATER MIN* - MAX
50-120 [10-49]
60-90 [16-43]
EXTENDED RANGE UNIT** EN-
TERING WATER MIN* - MAX
30-120 [-1-49]
20-90 [-6.7-43]
*- Requires optional insulation package when operating below the dew point
**- Requires antifreeze, optional insulation package and jumper clipped.
Table 6: Building Commissioning
Table 6A: Unit Operating Limits
Environment – This unit is designed for indoor installation only.
Do not install in an area subject to freezing or where humidity
levels can cause cabinet condensation.
Power Supply±$YROWDJHYDULDWLRQRIRIQDPHSODWH
utilization voltage is acceptable.
Operation and performance is primarily dependent upon return
DLUWHPSHUDWXUHDLUÀRZZDWHUWHPSHUDWXUHZDWHUÀRZUDWHDQG
ambient air temperature. This water to air heat pump is capable
RIRSHUDWLQJRYHUDZLGHWHPSHUDWXUHUDQJHDQGZLWKÀRZUDWHV
of between 1.5 GPM (.1 l/s) and 3 GPM (.19 l/s) per ton, however
usually no more than one of these factors may be at a minimum
or maximum level at a time.
The commissioning table indicates air and water temperatures
which are suitable for initial unit commissioning in an environment
ZKHUHWKHÀRZUDWHDQGZDWHUWHPSHUDWXUHLVQRW\HWVWDEOHDQG
to avoid nuisance shut down of the units freeze and refrigerant
pressure safeties.
The operating table indicates the maximum and minimum
ranges of the unit.
)RUPRUHVSHFL¿FXQLWSHUIRUPDQFHUHIHUHQFHWKHSURGXFWFDWDORJ
the submittal data sheets or contact your supplier for assistance.