Blower performance, Hkv 300 blower performance, Table continued from previous page – Comfort-Aire HKV300A User Manual
Page 40: Hkv series, Installation, operation & maintenance, Heat controller, llc
![background image](/manuals/463440/40/background.png)
Installation, Operation & Maintenance
HKV SERIES
Heat Controller, LLC
39
Blower Performance
HKV 300 Blower Performance
10600
BHP
3.68
3.88
4.08
4.28
4.48
4.68
4.88
5.08
5.28
5.48
5.68
5.88
6.18
6.38
6.58
6.78
10600
Sheave/Mtr
B
B
B
B
A
A
A
D
D
D
D
E
E
E
E
E
10600
RPM
680
709
737
763
790
817
842
867
889
912
935
957
979
1000
1021
1042
10600
Turns Open
4.5
3.5
3
2
5.5
4.5
4
3
2.5
2
1
3
2.5
2
1.5
1
10800
BHP
3.88
4.08
4.28
4.48
4.68
4.88
5.08
5.28
5.48
5.68
5.88
6.18
6.38
6.58
6.78
6.98
10800
Sheave/Mtr
B
B
B
A
A
A
D
D
D
D
E
E
E
E
E
E
10800
RPM
691
717
745
772
799
825
850
873
897
920
943
965
986
1006
1026
1047
10800
Turns Open
4.5
3.5
2.5
6
5
4.5
3.5
3
2
1.5
3.5
3
2.5
2
1.5
1
11000
BHP
4.08
4.28
4.48
4.68
4.88
5.08
5.28
5.48
5.68
6.18
6.28
6.48
6.68
6.88
7.08
7.38
11000
Sheave/Mtr
B
B
B
A
A
D
D
D
D
D
E
E
E
E
E
E
11000
RPM
704
729
756
783
810
836
859
883
907
929
952
972
993
1014
1035
1055
11000
Turns Open
3.5
3
2
5.5
5
4
3
2.5
2
1.5
3.5
3
2.5
2
1
0.5
11200
BHP
4.28
4.48
4.68
4.88
5.08
5.28
5.48
5.68
6.00
6.28
6.48
6.68
6.88
7.08
7.38
11200
Sheave/Mtr
B
B
A
A
D
D
D
D
D
D
E
E
E
E
E
11200
RPM
714
740
767
794
818
844
868
892
916
938
959
981
1002
1023
1043
11200
Turns Open
3.5
2.5
6
5.5
4.5
3.5
3
2.5
1.5
1
3
2.5
2
1.5
1
11400
BHP
4.48
4.68
4.88
5.08
5.28
5.48
5.78
6.08
6.28
6.48
6.68
6.88
7.18
7.48
11400
Sheave/Mtr
B
B
A
D
D
D
D
D
D
D
E
E
E
E
11400
RPM
726
752
779
803
829
854
878
902
925
948
970
990
1011
1031
11400
Turns Open
3
2
5.5
5
4.5
3.5
3
2
1.5
1
3
2.5
2
1.5
11600
BHP
4.68
4.88
5.08
5.28
5.48
5.68
6.00
6.28
6.48
6.68
6.88
7.18
7.48
11600
Sheave/Mtr
B
A
D
D
D
D
D
D
D
E
E
E
E
11600
RPM
738
763
788
813
839
864
888
911
934
955
977
998
1019
11600
Turns Open
2.5
6
5.5
4.5
4
3
2.5
2
1
3.5
2.5
2
1.5
11800
BHP
4.88
5.08
5.28
5.48
5.78
6.08
6.28
6.48
6.68
6.98
7.28
7.48
11800
Sheave/Mtr
B
D
D
D
D
D
D
D
D
E
E
E
11800
RPM
750
775
799
824
849
874
898
921
944
964
986
1007
11800
Turns Open
2
5.5
5
4
3.5
3
2.5
2
1
3
2.5
2
12000
BHP
5.08
5.28
5.48
5.78
6.08
6.28
6.48
6.68
6.98
7.28
7.48
12000
Sheave/Mtr
D
D
D
D
D
D
D
D
E
E
E
12000
RPM
758
783
808
833
858
880
904
927
950
972
993
12000
Turns Open
6
5.5
4.5
4
3.5
2.5
2
1.5
3.5
3
2.5
12200
BHP
5.28
5.48
5.78
6.08
6.28
6.48
6.68
6.98
7.28
7.48
12200
Sheave/Mtr
D
D
D
D
D
D
D
D
E
E
12200
RPM
769
794
819
843
866
890
913
936
958
980
12200
Turns Open
6
5
4.5
4
3
2.5
2
1.5
3
2.5
12400
BHP
5.68
5.88
6.08
6.28
6.48
6.78
7.08
7.28
7.48
12400
Sheave/Mtr
D
D
D
D
D
D
D
D
E
12400
RPM
781
815
830
854
878
900
923
946
968
12400
Turns Open
5.5
4.5
4.5
3.5
3
2
1.5
1
3
12600
BHP
5.88
6.08
6.28
6.58
6.88
7.08
7.28
12600
Sheave/Mtr
D
D
D
D
D
D
D
12600
RPM
793
817
841
863
886
910
933
12600
Turns Open
5
4.5
4
3
2.5
2
1.5
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
All Data is Wet Coil
Table Continued from Previous Page