Unit & System Checkout
slag, and strong chemical cleaning agents. Verify all air is
purged from the system. Air in the system can cause poor
operation or system corrosion.
Cooling Tower/Boiler: Check equipment for proper set-
points and operation.
Standby Pumps: Verify the standby pump is properly
installed and in operating condition.
System Controls: Verify system controls function and
operate in the proper sequence.
Low Water Temperature Cutout: Verify low water tempera-
WARNING! Verify ALL water controls are open and allow
ZDWHUÀRZSULRUWRHQJDJLQJWKHFRPSUHVVRU)UHH]LQJRI
the coax or water lines can permanently damage the heat
pump.
WARNING! To avoid equipment damage, DO NOT leave
V\VWHP¿OOHGLQDEXLOGLQJZLWKRXWKHDWGXULQJWKHZLQWHU
unless antifreeze is added to system water. Condenser
coils never fully drain by themselves and will freeze unless
winterized with antifreeze.
ture cut-out controls are provided for the outdoor portion
of the loop or operating problems will occur.
System Control Center: Verify control center and alarm
panel for proper setpoints
and operation (if used).
Miscellaneous: Note any questionable aspects of the
installation.
Log Data: Record data on startup log sheet in this manual.
keep log for future reference.
WARNING!
!
!