Blower performance, Hkv 096 blower performance, Table continued on next page – Comfort-Aire HKV300A User Manual
Page 28: Hkv series, Installation, operation & maintenance, Heat controller, llc
Installation, Operation & Maintenance
HKV SERIES
Heat Controller, LLC
27
HKV 096 Blower Performance
All Data is Wet Coil
Airflow
(SCFM)
ESP
Airflow (cfm) at External Static Pressure (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
2400
BHP
0.29
0.34
0.39
0.44
0.49
0.54
0.59
0.64
0.69
0.74
0.79
0.84
0.89
0.94
0.99
2400
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
2400
RPM
403
446
485
527
563
600
633
665
697
726
756
783
811
835
858
2400
Turns Open
5
4
3
6
5.5
4.5
3.5
2.5
1.5
1
5.5
5
4
3.5
3
2500
BHP
0.31
0.34
0.39
0.44
0.49
0.54
0.59
0.64
0.74
0.79
0.84
0.89
0.94
0.99
1.04
2500
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
2500
RPM
411
452
495
532
567
604
636
670
700
729
759
786
813
838
864
2500
Turns Open
5
4
2.5
6
5.5
4
3.5
2.5
1.5
1
5.5
5
4
3
3
2600
BHP
0.34
0.43
0.48
0.53
0.58
0.63
0.68
0.73
0.78
0.83
0.88
0.93
1.03
1.08
1.13
2600
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
2600
RPM
420
460
500
536
570
606
638
671
701
729
759
786
814
839
865
2600
Turns Open
4.5
3.5
2.5
6
5
4
3
2
1.5
1
5
5
4
3
2.5
2700
BHP
0.38
0.43
0.48
0.53
0.59
0.64
0.69
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.14
2700
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
2700
RPM
423
463
504
539
576
609
641
674
703
734
762
788
816
841
867
2700
Turns Open
4.5
3.5
2
5.5
5
4
3
2
1.5
1
5
4.5
4
3
2.5
2800
BHP
0.39
0.44
0.49
0.54
0.64
0.69
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.12
1.22
2800
Sheave/Mtr
B
B
B
A
A
A
A
A
A
C
C
C
C
C
C
2800
RPM
431
474
510
545
581
613
647
677
706
737
764
793
818
843
869
2800
Turns Open
4.5
3
2
5.5
5
4
3
2
1.5
5.5
5
4.5
3.5
3
2.5
2900
BHP
0.44
0.49
0.54
0.59
0.64
0.74
0.79
0.84
0.89
0.94
1.04
1.09
1.14
1.19
1.24
2900
Sheave/Mtr
B
B
B
A
A
A
A
A
A
C
C
C
C
C
2900
RPM
440
481
517
551
586
618
651
681
710
740
767
795
821
845
872
2900
Turns Open
4
3
2
5.5
4.5
3.5
2.5
1.5
1
5.5
5
4.5
3.5
2.5
2.5
3000
BHP
0.43
0.49
0.54
0.59
0.64
0.69
0.74
0.84
0.89
0.94
1.04
1.09
1.14
1.19
1.24
1.29
3000
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
3000
RPM
412
455
492
526
563
595
628
658
687
718
745
774
800
826
852
876
3000
Turns Open
5
3.5
2.5
6
5.5
4.5
3.5
2.5
1.5
1.5
6
5
4
3.5
2.5
2
3100
BHP
0.44
0.53
0.59
0.64
0.69
0.74
0.84
0.89
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.39
3100
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
3100
RPM
421
459
499
533
569
600
633
663
691
722
749
777
803
828
854
878
3100
Turns Open
4.5
3.5
2.5
6
5
4
3
2
1.5
1.5
6
4.5
4
3
2.5
2
3200
BHP
0.49
0.54
0.64
0.69
0.74
0.84
0.89
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.39
1.44
3200
Sheave/Mtr
B
B
B
A
A
A
A
A
A
A
C
C
C
C
C
C
3200
RPM
441
478
513
549
581
614
644
672
703
730
759
785
810
837
861
887
3200
Turns Open
4
3
2
5.5
5
4
3
2
1.5
1.5
5.5
4.5
4
3
2.5
2
3300
BHP
0.54
0.64
0.69
0.74
0.83
0.89
0.94
0.99
1.04
1.14
1.23
1.29
1.34
1.44
1.49
1.54
3300
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
C
C
C
C
C
E
3300
RPM
456
495
529
561
595
625
656
685
712
741
767
795
820
844
870
893
3300
Turns Open
3.5
2.5
6
5
4.5
3.5
2.5
2
1.5
1
5
4.5
3.5
3
2
2
3400
BHP
0.63
0.69
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.44
1.49
1.54
1.64
3400
Sheave/Mtr
B
B
A
A
A
A
A
A
A
A
C
C
C
C
E
E
3400
RPM
471
506
539
574
604
633
664
692
721
747
773
800
825
851
875
898
3400
Turns Open
3
2
5.5
5
4
3.5
2.5
2
1.5
1
5
4
3.5
2.5
2.5
2
3500
BHP
0.64
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.23
1.29
1.34
1.44
1.49
1.54
1.64
1.74
3500
Sheave/Mtr
B
A
A
A
A
A
A
A
A
C
C
C
C
E
E
E
3500
RPM
486
520
555
586
615
647
674
704
730
756
784
808
835
858
883
906
3500
Turns Open
2.5
6
5.5
4.5
4
3
2.5
1.5
1
5.5
4.5
4
3
2.5
2.5
1.5
3600
BHP
0.74
0.79
0.84
0.94
0.99
1.04
1.14
1.19
1.24
1.34
1.44
1.49
1.54
1.64
1.74
1.83
3600
Sheave/Mtr
B
A
A
A
A
A
A
A
A
C
C
C
E
E
E
E
3600
RPM
495
528
562
593
624
652
680
708
734
762
787
812
838
861
886
909
3600
Turns Open
2.5
6
5
4.5
3.5
3
2
1.5
1
5.5
4.5
4
3
2.5
2.5
1.5
3700
BHP
0.79
0.84
0.93
0.99
1.04
1.14
1.19
1.24
1.34
1.44
1.49
1.54
1.64
1.74
1.79
1.84
3700
Sheave/Mtr
B
A
A
A
A
A
A
A
A
C
C
E
E
E
E
E
3700
RPM
506
541
572
605
633
661
690
716
744
769
793
820
843
868
891
913
3700
Turns Open
2
5.5
5
4
3.5
3
2
1.5
1
5
4.5
3.5
3
2.5
2
1.5
Table Continued on Next Page
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions. Do not operate in black regions. All
airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Blower Performance