Address
Description
SuperView Mnemonic
Minimum
Maximum
R/W
70
Counted pulses in the last interval for input 4 - least
significant word
PulseRate4L
0
65535
R
71
Maximum of pulses counted on time interval for input
1 - most significant word
PeakPulse1H
0
65535
R
72
Maximum of pulses counted on time interval for input
1 - least significant word
PeakPulse1L
0
65535
R
73
Maximum of pulses counted on time interval for input
2 - most significant word
PeakPulse2H
0
65535
R
74
Maximum of pulses counted on time interval for input
2 - least significant word
PeakPulse2L
0
65535
R
75
Maximum of pulses counted on time interval for input
3 - most significant word
PeakPulse3H
0
65535
R
76
Maximum of pulses counted on time interval for input
3 - least significant word
PeakPulse3L
0
65535
R
77
Maximum of pulses counted on time interval for input
4 - most significant word
PeakPulse4H
0
65535
R
78
Maximum of pulses counted on time interval for input
4 - least significant word
PeakPulse4L
0
65535
R
79-84
Reserved
-
0
0
R
DETAILS OF SOME REGISTERS
REGISTER 2 – BAUD RATE
Code of speed used in Modbus communication.
Code
Baud rate
0
1.200
1
2.400
2
4.800
3
9.600
4
19.200
5
38.400
6
57.600
7
115.200
REGISTER 3 – MODBUS ADDRESS
Address of the device in the Modbus network. Valid values: from 1 to 247. We recommend using the lower addresses for
the equipment.
REGISTER 4 – PARITY
Code of the parity used in Modbus communication.
Code
Parity
0
No parity
1
Odd
2
Even
REGISTER 5 – FIRMWARE VERSION
Indicates the firmware version of the equipment, according to the examples below:
If the version is "1.00", the value "100" will be read. If the version is "2.04", the value "204" will be read.
REGISTER 6 – DIAGNOSTIC STATE TIMER
Internally used by the DigiConfig software.
REGISTER 7 – STATE OF THE DIGITAL INPUTS
Bit at 0: Input deactivated
Bit at 1: Input activated
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Entry
-
-
-
-
-
-
- - - - - - 4 3 2 1