0104
Bytes 0 and 1 of channel 6 string (tag)
0105
Bytes 2 and 3 of channel 6 string (tag)
0106
Bytes 4 and 5 of channel 6 string (tag)
0107
Bytes 6 and 7 of channel 6 string (tag)
0108
Bytes 0 and 1 of channel 7 string (tag)
0109
Bytes 2 and 3 of channel 7 string (tag)
0110
Bytes 4 and 5 of channel 7 string (tag)
0111
Bytes 6 and 7 of channel 7 string (tag)
0112
Bytes 0 and 1 of channel 8 string (tag)
0113
Bytes 2 and 3 of channel 8 string (tag)
0114
Bytes 4 and 5 of channel 8 string (tag)
0115
Bytes 6 and 7 of channel 8 string (tag)
0116
Bytes 0 and 1 of the engineering unit of channel 1
0117
Bytes 2 and 3 of the engineering unit of channel 1
0118
Bytes 4 and 5 of the engineering unit of channel 1
0109
Bytes 6 and 7 of the engineering unit of channel 1
0120
Bytes 0 and 1 of the engineering unit of channel 2
0121
Bytes 2 and 3 of the engineering unit of channel 2
0122
Bytes 4 and 5 of the engineering unit of channel 2
0123
Bytes 6 and 7 of the engineering unit of channel 2
0124
Bytes 0 and 1 of the engineering unit of channel 3
0125
Bytes 2 and 3 of the engineering unit of channel 3
0126
Bytes 4 and 5 of the engineering unit of channel 3
0127
Bytes 6 and 7 of the engineering unit of channel 3
0128
Bytes 0 and 1 of the engineering unit of channel 4
0129
Bytes 2 and 3 of the engineering unit of channel 4
0130
Bytes 4 and 5 of the engineering unit of channel 4
0131
Bytes 6 and 7 of the engineering unit of channel 4
0132
Bytes 0 and 1 of the engineering unit of channel 5
0133
Bytes 2 and 3 of the engineering unit of channel 5
0134
Bytes 4 and 5 of the engineering unit of channel 5
0135
Bytes 6 and 7 of the engineering unit of channel 5
0136
Bytes 0 and 1 of the engineering unit of channel 6
0137
Bytes 2 and 3 of the engineering unit of channel 6
0138
Bytes 4 and 5 of the engineering unit of channel 6
0139
Bytes 6 and 7 of the engineering unit of channel 6
0140
Bytes 0 and 1 of the engineering unit of channel 7
0141
Bytes 2 and 3 of the engineering unit of channel 7
0142
Bytes 4 and 5 of the engineering unit of channel 7
0143
Bytes 6 and 7 of the engineering unit of channel 7
0144
Bytes 0 and 1 of the engineering unit of channel 8
0145
Bytes 2 and 3 of the engineering unit of channel 8
0146
Bytes 4 and 5 of the engineering unit of channel 8
0147
Bytes 6 and 7 of the engineering unit of channel 8
0152
Decimal point position for channels
0199
Software version
NOTES ABOUT REGISTERS
Registers 00 to 07:
They keep the continuously updated value of readings from their
respective input channels. The speed of such update depends on the
number of channels enabled and the input type selected for such
channels. As the register is constantly scanning inputs, the higher the
number of active channels the higher the number of inputs that will
be read until the device reads the same channel again, decreasing
the update speed. Besides, channels configured as Pt100 are read
twice each, as part of a compensation algorithm of the cable
resistance. In cases where there is only one active channel (non-
defined as Pt100), this channel is updated at every 0.2 seconds (best
rate). In the case of eight Pt100 channels (worst rate), complete
scanning of channels takes 0.95 seconds.
The signal of the value read is represented as complement of 2.
In cases with resolutions in tenth of degrees, such as Pt100 and
thermocouples, the value is read without the decimal point (multiplied
by 10), for protocol constraints. The same way, the decimal point is
disregarded in linear inputs (4-20 mA e 0-50 mV).
Register 08:
Reports if there is an alarm event in some of the channels and if the
event corresponds to a Low or High alarm.
byte high:
byte low:
Registers 10 to 13
Report A/D conversion errors.
byte high
→
odd channel:
byte low
→
even channel:
Same as byte high for the adjacent channel.