beautypg.com

7 special care – NOVUS RHT-P10-485-LCD User Manual

Page 5

background image

RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P10-485-LCD Transmitters

NOVUS AUTOMATION

5/6

HOLDING REGISTERS TABLE

The specified addresses correspond to the low-level physical addresses, where zero (0) corresponds to the PLC 40001 address. The minimum and maximum

columns show the range of values valid for each parameter. The R/W column indicates if the parameter is for reading and writing (R/W) or for reading only (R).

Address

Description

Minimum

Maximum

R/W

0

Serial number (word high)

0

65535

R

1

Serial number (word low)

0

65535

R

2

Baud-Rate

0

7

R/W

3

Modbus Address

1

247

R/W

4

Parity

0

2

R/W

5

Firmware release

0

999

R

6

Indication mode

0

3

R/W

7

Temperature value (ºC or ºF).

*

-400

1000

R

8

Relative humidity value (%).

*

0

1000

R

9

Dew point value (ºC or ºF).

*

-400

1000

R

10

Configuration of measurement unit

0

1

R/W

11

Disables configuration via button

0

1

R/W

12

User offset for temperature

*

-100

100

R/W

13

Reserved

0

0

R

14

User offset for humidity

*

-100

100

R/W

15

Reserved

16

Error value

-9999

9999

R/W

17

Title

-

-

R/W

18

Title

-

-

R/W

19

Title

-

-

R/W

20

Title

-

-

R/W

21

Title

-

-

R/W

62

Model

0

11

R

*

For the ranges indicated above consider with one decimal place. Example: -100 means -10.0

REGISTER 6 – INDICATION MODE
Defines the indication mode on the display of the sensor values readout. The

transmitter comes factory-configured with indication of temperature and

relative humidity.

Code

Description

0

Indicates temperature and relative humidity.

1

Indicates temperature and dew point.

2

Indicates relative humidity and dew point.

3

Indicates temperature only.

REGISTER 7 – TEMPERATURE VALUE (ºC or ºF)

REGISTER 8 – RELATIVE HUMIDITY VALUE (%)

REGISTER 9 – DEW POINT VALUE (ºC or ºF)
Shows the measured value in engineering units. The decimal point is fixed at

one place, the value is exhibited without the decimal point and must be

considered by the reading software.

REGISTER 10 – CONFIGURATION OF MEASUREMENT UNIT
Defines the measurement unit for the temperature and the dew point. The

transmitter comes factory-configured for degrees Celsius (°C).

Code

Unit

0

ºC

1

ºF

REGISTER 11 – DISABLES CONFIGURATION VIA BUTTON
Defines the changes of configuration via button.

Code

Description

0

Factory-configured default value

1

Disables the configuration change of

communication parameters via button.

REGISTER 12 – USER OFFSET FOR TEMPERATURE
Defines the user offset value in engineering units for the temperature. The

transmitter comes factory-configured with the offset value equal to zero.

REGISTER 14 – USER OFFSET FOR HUMIDITY
Defines the user offset value in engineering units for the relative humidity.

The transmitter comes factory-configured with the offset value equal to zero.

REGISTER 16 – ERROR VALUE
Shows the error value which is transmitted when the sensor has a problem.

The transmitter comes factory-configured with the value -9999.

7 SPECIAL CARE

The transmitter is an electronic module and, therefore, will need some

special care when handling it:

• When you open the transmitter to fix it, avoid any contact with the

electronic circuit due to the risk of damage caused by static electricity.

• Take maximum care when connecting the wires.
• When you close the case, the cover must be replaced correctly, thus

assuring the sealing quality of this model.

This manual is related to the following products: