NOVUS N120/N125 CONTROLLER User Manual
Page 2

2
0023
Serial
number H
Serial Number High (Upper display).
Range: 0 to 9999. Read only.
0024
Serial
number L
Serial Number Low (Lower display).
Range: 0 to 9999. Read only.
0025
SV
Control Setpoint (Prompt Setpoint).
Range: from spll to spkl.
0026
spll
Setpoint Low limit.
Range: minimum value depends on the input type selected
in type (see Table 1) to spkl.
0027
spkl
Setpoint High limit.
Range: minimum value is spll and maximum depends on
the input type selected in type (see Table 1).
0028
Reserved
Internal use.
0029
offs
Offset value of PV(Process value).
Range: from spll to spkl.
0030
dppo
PV decimal point position
Range: 0 to 3
0
0.000; 1
00.00; 2
000.0; 3
0000
0031
Sp.a1
Alarm 1 Setpoint.
Range: From spll to spkl for non differential; and
spkl
- spll for differential alarm.
0032
Sp.a2
Alarm 2 Setpoint. Range: same as in spa1.
0033
Sp.a3
Alarm 3 Setpoint. Range: same as in spa1.
0034
Sp.a4
Alarm 4 Setpoint. Range: same as in spa1.
0035
Fva1
Alarm 1 Function. Range: 0 to 8
0
off
1
ierr
2
T.END
3
rs
4
lo
5
ki
6
dif
7
difl;
8
difk;
0036
Fva2
0037
Fva3
0038
Fva4
0039
Kya1
Alarm 1 Hysteresis. Range: 0 to 9999 (0.00 to 99.99%)
0040
Kya2
Alarm 2 Hysteresis. Range: same as in kya1.
0041
Kya3
Alarm 3 Hysteresis. Range: same as in kya1.
0042
Kya4
Alarm 4 Hysteresis. Range: same as in kya1.
0043
type
PV input type:
0 = J
1 = K
2 = T
3 = N
4 = R
5 = S
6 = B
7 = E
8 = Pt100
9 = 0-20 mA
10 = 4-20 mA
11 = 0-50 mV
12 = 0-5 V
13 = 0-10 V
0044
addr
Communication slave address. Range: 1 to 247
0045
bavd
Communication Baud-Rate:
0
1200;1
2400;2
4800;3
9600; 4
19200;
5
38400; 6
57600; 7
115200;
0046
avto
Control Mode. Range: 0
manual; 1
automatic.
0047
rvn
Enable control. Range: 0
no; 1
yes.
0048
act
Control action. Range: 0
direct; 1
reverse.
0049
atvn
Auto tune enable:
0= off;1= Fast; 2= Full; 3= Self; 4= rSLF; 5= tGHt;
0050
Bla1
Alarm power-up inhibit. Range: 0
no; 1
yes.
0051
Bla2
0052
Bla3
0053
Bla4
0054
Key
Key press remote action. Range: 0 to 9
1: tecla P
2: tecla
4: tecla
8: tecla B
9: teclas P e B
0062
A1t1
Alarm 1 Time 1. Range: 0 to 6500s.
Refer to operation manual for more details.
0063
A1t2
Alarm 1 Time 2 (in seconds).
Range: same as in a1t1.
0064
A2t1
Alarm 2 Time 1 (in seconds).
Range: same as in a1t1.
0065
A2t2
Alarm 2 Time 2 (in seconds).
Range: same as in a1t1.
0066
sfst
Soft-Start time (in seconds).
Range: 0 to 9999
0067
vnit
Temperature unit. Range: 0 to 1.
0
C; 1
F.
0068
bias
Bias. Range: -100 to +100%.
0070
R&S
Segment
Ramp and Soak segment being executed (read only).
Range: 0 to 9.
0071
Pr n
Ramp and Soak segment to be viewed or edited.
Range: 1 to 20.
0072
E pr
Ramp and Soak segment to be executed.
Range: 0 to 20.
0073 Remaining time
R&S
Indicates the remaining time of the Ramp and Soak
segment.
0074
Sqrt
Square root of a linear input.
Range: 0->Disable;1->Enable.
0075
Calibration PV
Low
Enter the low input value currently applied in the PV input
for calibration purposes.
0076
Calibration PV
High
Enter the high input value currently applied in the PV input
for calibration purposes.
0077
Calib. remote
SP Low
Enter the low input value currently applied in the remote
setpoint input for calibration purposes.
0078
Calib. remote
SP High
Enter the high input value currently applied in the remote
setpoint input for calibration purposes.
0081
FLSH
Enables the top display blinking as a function of the
selected alarm:
0-> Disable
1-> Enable to alarm 1
2-> Enable to alarm 2
3-> Enable to alarm 1 and 2
0086
Rstr
Restores original default calibration.
Range: 0 to 1; 0-> do not restore; 1-> restore calibration