Beijer Electronics BFI-P2 V1.21 User Manual

Page 47

background image

User Guide Revision 1.121 

 

www.beijerelectronics.com 

47 

 

9.2.2. Modbus Control & Monitoring Registers 

The following is a list of accessible Modbus Registers available in the Drive.  

When Modbus RTU is configured as the Fieldbus option, all of the listed registers can be accessed.  

Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source (P1‐12 = 4) 
and no Fieldbus Option Module is installed in the drive Option Slot. 

Register 3 can be used to control the output torque level providing that  

o

The drive is operating in Vector Speed or Vector Torque motor control modes (P4‐01 = 1 or 2) 

o

The torque controller reference / limit is set for ‘Fieldbus’ (P4‐06 = 3) 

Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is enabled 
(P5‐07 = 1) 

Registers 6 to 24 can be read regardless of the setting of P1‐12 

Register 
Number 

Upper Byte 

Lower Byte 

Read 

Write 

Notes 

1

 

Command Control Word 

R/W 

Command control word used to control the Drive when operating with Modbus RTU. 
The Control Word bit functions are as follows :‐ 
Bit 0 : Run/Stop command. Set to 1 to enable the drive. Set to 0 to stop the drive. 
Bit 1 : Fast stop request. Set to 1 to enable drive to stop with 2

nd

 deceleration ramp. 

Bit 2 : Reset request. Set to 1 in order to reset any active faults or trips on the drive.  
This bit must be reset to zero once the fault has been cleared. 
Bit 3 : Coast stop request. Set to 1 to issue a coast stop command. 

2

 

Command Speed Reference 

R/W 

Setpoint must be sent to the drive in Hz to one decimal place, e.g. 500 = 50.0Hz 

3

 

Command Torque Reference 

R/W 

Setpoint must be sent to the drive in % to one decimal place, e.g. 2000 = 200.0% 

4

 

Command Ramp times 

R/W 

This register specifies the drive acceleration and deceleration ramp times used when 
Fieldbus Ramp Control is selected (P5‐08 = 1) irrespective of the setting of P1‐12. The 
input data range is from 0 to 60000 (0.00s to 600.00s) 

6

 

Error code

 

Drive status

This register contains 2 bytes.  
The Lower Byte contains an 8 bit drive status word as follows :‐ 
Bit 0 : 0 = Drive Disabled (Stopped), 1 = Drive Enabled (Running)  
Bit 1 : 0 = Drive Healthy, 1 =  Drive Tripped 
The Upper Byte will contain the relevant fault number in the event of a drive trip. 
Refer to section Error! Reference source not found. for a list of fault codes and 
diagnostic information 

7

 

Output Frequency 

Output frequency of the drive to one decimal place, e.g.123 = 12.3 Hz 

8

 

Output Current 

Output current of the drive to one decimal place, e.g.105 = 10.5 Amps 

9

 

Output Torque 

Motor output torque level to one decimal place, e.g. 474 = 47.4% 

10

 

OutputPower 

Output power of the drive to two decimal places, e.g.1100 = 11.00 kW 

11

 

Digital Input Status 

Represents the status of the drive inputs where Bit 0 = Digital Input 1 etc. 

20

 

Analog 1 Level 

Analog Input 1 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0% 

21

 

Analog 2 Level 

Analog Input 2 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0% 

22

 

Pre Ramp Speed Reference 

Internal drive frequency setpoint 

23

 

DC bus voltages 

Measured DC Bus Voltage in Volts 

24

 

Drive temperature 

Measured Heatsink Temperature in °C 

9.2.3. Modbus Parameter Access 

All User Adjustable parameters (Groups 1 to 5) are accessible by Modbus, except those that would directly affect the Modbus communications, 
e.g. 

P5‐01 Communication Protocol Select 

P5‐02 Drive Fieldbus Address 

P5‐03 Modbus RTU Baud Rate 

P5‐04 Modbus RTU Data Format 

All parameter values can be read from the drive and written to, depending on the operating mode of the drive – some parameters cannot be 
changed whilst the drive is enabled for example. 
 
When accessing a drive parameter via Modbus, the Register number for the parameter is the same as the parameter number,  
E.g. Parameter P1‐01 = Modbus Register 101. 
Modbus RTU supports sixteen bit integer values, hence where a decimal point is used in the drive parameter, the register value will be multiplied 
by a factor of ten, 
E.g. Read Value of P1‐01 = 500, therefore this is 50.0Hz. 
 
For further details on communicating with Drive using Modbus RTU, please refer to your local distributor or Sales Partner.