4.10.4. “STO“  Operation  

When the “STO” inputs are energised, the “STO” function is in a standby state, if the drive is then given a “Start signal/command” (as per the 
start source method selected in P1‐13) then the drive will start and operate normally.  
 

When the “STO” inputs are de‐energised then the STO Function is activated and stops the drive (Motor will coast), the drive is now in “Safe 
Torque Off” mode. 
 
To get the drive out of “Safe Torque Off” mode then any “Fault messages” need to be reset and the drive “STO” input needs to be re‐energised. 

4.10.5. “STO” Status and Monitoring 

There are a number of methods for monitoring the status of the “STO” input, these are detailed below: 
Drive Display  
In Normal drive operation (Mains AC power applied), when the drives “STO” input is de‐energised (“STO” Function activated) the drive will 
highlight this by displaying “InHibit”, (Note: If the drive is in a tripped condition then the relevant trip will be displayed and not “InHibit”). 
Drive Output Relay 

• Drive relay 1: Setting P2‐15 to a value of “13” will result in relay opening when the “STO” function is activated. 
• Drive relay 2: Setting P2‐18 to a value of “13” will result in relay opening when the “STO” function is activated. 

 
“STO” Fault Codes 

Fault 
Code 

Code  

Number  

Description 

Corrective Action 

“Sto‐F” 

29

 

A fault has been detected within either of the 

internal channels of the “STO” circuit. 

Refer to your Beijer Sales Partner 

4.10.6. “STO” Function response time 

The total response time is the time from a safety related event occurring to the components (sum of) within the system responding and 
becoming safe. (Stop Category 0 in accordance with IEC 60204‐1) 
 

The response time from the “STO” inputs being de‐energised to the output of the drive being in a state that will not produce torque in 
the motor (“STO” active) is less than 1ms. 

The response time from the “STO” inputs being de‐energised to the “STO” monitoring status changing state is less than 20ms 

The response time from the drive sensing a fault in the STO circuit to the drive displaying the fault on the display/Digital output 
showing drive not healthy is less than 20ms.