Ip55 quick start up guide – Beijer Electronics BFI-P2 V1.21 User Manual
Page 3

User Guide Revision 1.121
www.beijerelectronics.com
3
IP55 Quick Start Up Guide
Display
Keypad Operation can be found
on page 27
IMPORTANT
Hardware Enable Circuit
Link the terminals as shown
above, optionally through switch
contacts to enable drive operation
AC Supply Connection
Control Terminals
200 – 240 Volts + / ‐ 10%
380 – 480 Volts + / ‐ 10%
L3 L2 L1 PE
Run / Stop 10K Pot
Close the switch to run (enable)
Open the switch to stop
Fuses or MCB
Motor Cable
Check drive
For correct cable size, see
Rating info on
Technical Data on page 48
Page 48
Observe the maximum permissible motor
cable length
For Motor cable lengths > 50 metres, an
output filter is recommended
Use a screened (shielded) cable. The shield
should be bonded to earth at both ends
Motor Connection
Check for Star or Delta Connection
Enter the Motor Nameplate Data into the
drive Parameters as follows
Motor Rated Voltage : P1‐07
Motor Rated Current : P1‐08
Motor Rated Frequency : P1‐09
Motor Rated Speed (Optional) : P1‐10
M