Ip66 easy start up guide – Beijer Electronics BFI-P2 V1.21 User Manual
Page 4

User Guide Revision 1.12
www.beijerelectronics.com
4
IP66 Easy Start Up Guide
Display
Keypad Operation can be found
on page 27
IMPORTANT
Hardware Enable Circuit
Link the terminals as shown,
optionally through switch
contacts to enable drive operation
Control Terminals
Run / Stop 10K Pot
Close the switch to run (enable)
Open the switch to stop
Motor Cable
For correct cable size, see
Technical Data on page 48
Observe the maximum permissible motor
cable length
Fuses or MCB
For Motor cable lengths > 50 metres, an
Check Drive Rating
output filter is recommended
Information on
Use a screened (shielded) cable. The shield
Page 48
should be bonded to earth at both ends
Motor Connection
Check for Star or Delta Connection
AC Supply Connection
Enter the Motor Nameplate Data into the
200 – 240 Volts + / ‐ 10%
drive Parameters as follows
380 – 480 Volts + / ‐ 10%
Motor Rated Voltage : P1‐07
Motor Rated Current : P1‐08
Motor Rated Frequency : P1‐09
Motor Rated Speed (Optional) : P1‐10
M