Installation

Gas Connection

PRESSURE REGULATION AND TESTING
Each section of the 1060-B series oven is rated at 85,000

BTU per hour (24.9 kW). At full demand, each section

1060-BL oven requires 85 cubic feet per hour (2.4 m3)

Natural gas or 33 cubic feet per hour (0.9 m3) Propane

gas. Each oven has been adjusted at the factory to oper-

ate with the type of gas specified on the rating plate.

INLET PRESSURE

Natural

Propane

Min

Max

Min

Max

W.C.

7.0

10.5

11.0

13.0

kPa

1.43

2.61

2.74

3.23

MANIFOLD PRESSURE

Natural

Propane

W.C.

3.5

10.0

kPa

.87

2.49

• Inlet Pressure - the pressure of the gas before it

reaches the oven.

• Manifold Pressure - the pressure of the gas as it

enters the main burner(s).

• Min - the minimum pressure recommended to oper-

ate the oven.

• Max - the maximum pressure at which the manufac-

turer warrants the oven’s operation.

Each oven is supplied with a regulator to maintain the

proper gas pressure.

The regulator is essential to the

proper operation of the oven and must be installed.

It is preset to provide the oven with 3.5” W.C. (0.87 kPa)

for natural gas and 10.5” W.C. (2.50 kPa) for Propane at

the manifold.
DO NOT INSTALL AN ADDITIONAL REGULATOR

WHERE THE OVEN CONNECTS TO THE GAS SUP-

PLY UNLESS THE SUPPLY EXCEEDS THE MAXIMUM

PRESSURE.
Due to the decrease in oxygen at higher elevations,

above 2000’, the unit may need to be rerated. (The orifice

size may need to be adjusted to accomodate different air

pressures at higher elevations.) If not rerated, incomplete

combustion may occur releasing Aldehydes and CO or

Carbon Monoxide.

Any of these are unacceptable and

may be hazardous to the health of the operator.
Prior to connecting the oven, gas lines should be thor-

oughly purged of all metal filings, shavings, pipe dope,

and other debris. After connection, the oven should be

checked for correct gas pressure.
Installation must conform with local codes, or in the ab-

sence of local codes, with the National Fuel Gas Code,

NFPA54/ANSI Z223.1-Latest Edition, the Natural Gas In-

stallation Code CAN/CGA-B149.1 or the Propane Instal-

lation Code, CAN/CGA-B149.2 as applicable.
The oven and its individual shutoff valve must be discon-

nected from the gas supply piping system during any

pressure testing of that system at test pressures in ex-

cess of 1/2 psig (3.45kPa).
The oven must be isolated from the gas supply piping

system by closing its individual manual shutoff valve dur-

ing any pressure testing of the gas piping system at test

pressures equal or less than 1/2 psig (3.45kPa).