c. Strip the three wires in the cable tray coming from the DC input

power source to 8 millimeters

±

1 millimeters (0.31 inches

±

0.039

inches) using a 14-gauge wire-stripping tool.

Warning
Do not strip more than the recommended amount of wire. Stripping
more than the recommended amount can create a safety hazard by
leaving exposed wire on the terminal block after installation.

!

17

Figure 8 Stripped Wire

d. Connect the frame ground wire to the terminal marked with the

ground symbol by inserting the wire into the terminal block and
tightening the connection with a flathead screwdriver. See Figure 9.

Warning
When installing this equipment, always ensure that the frame ground
connection is installed first and disconnected last.

!

18

Figure 9 Connecting the Stripped Wire

8 mm ± 1 mm

(0.31 in ± 0.039 in)