beautypg.com

ARI Armaturen ARI-PACO 0,85kN EN User Manual

Page 14

background image

Page 14

0040506000 1811

Operating and installation instructions

Electric thrust actuator ARI-PACO 0,85 kN

5.4.3.1 ARI-PACO 0,85 D
- Connect the ground line of the connection lead to connector 1 of the connection strip of

the linear actuators

- Connect the impulse lead for the extended thrust rod on connector 2 of the connection

strip terminal.

- Connect the impulse lead for the retracted thrust rod on connector 3 of the connection

strip terminal.

-

Ρeplace housing carefully from above and mount with two recessed screws on the linear

actuator.

- Set sliding switch on the housing to automatic operation.
- Connect the supply lines to the mains and move the linear actuator into each of the end

positions in order to test if the end position switches shut off, and if the direction of
movement of the linear actuators is as desired.

- In case the direction of movement is opposite to that which is desired, the impulse cables

for the extending and the retracting thrust rod should be exchanged.

5.4.3.2 ARI-PACO 0,85 Y
- Connect the 24 V AC - voltage supply an connector 1 and V terminals (connector 1 = 0 V)
- Connect the control with a continuous signal of 0(2)...10 V on connector 1 and Y

terminals. (connector 1= 0 V)

- Connect the actuating output signal 0...10 V on connector 1 and A terminals (connector 1=

0 V).

- For priority switching (frost protection limitation) for retracted thrust rod on connector

1 and 2 terminals.

- For priority switching (frost protection limitation) for extended thrust rod on

connector 1 and 3 terminals.

- Replace housing carefully from above and mount with two recessed screws on the linear

actuator.

- Set sliding switch on the housing to automatic operation.
- Connect leads to mains and actuating signal

Carry out an initialization run (refer to 6.2.1 )