beautypg.com

Pplications – Red Lion PAXLPV User Manual

Page 8

background image

Example 1 (± Display):

A differential pressure transducer has a range of ±15 PSI with a 1-6 V

output (-15 @ 1 V, +15 @ 6 V)

READOUT SPAN (Rs) = +1500 - (-1500) = 3000
SWING VOLTAGE (Vs) = 6 V (max) - 1 V (min) = 5 V
SPAN PER VOLT (Rs/Vs) = 3000 / 5 V = 600

Note: Since the display readout is limited to 1999 numerical indication, the

full READOUT SPAN of 3000 cannot be obtained during zero based span
adjustment. However, dividing both the READOUT SPAN and SWING
VOLTAGE by two, i.e. 1500 readout @ 2.5 V, allows the span adjustment
to be made for the proper transfer curve slope.

ADJUSTMENTS

Null the unit to zero readout @ 0 V per
Steps 1 to 4 of the calibration steps.

Set transfer curve slope with span

adjustments per Steps 5 and 6 to get a
readout of +1500 @ 2.5 V (SPAN PER
VOLT = 600).

Apply (-) offset per Step 7 to get a

reading of -1500 @ 1 V.

Check min. and max. extremes and tweak

if required to get desired readout @ 1 V
and 6 V per step 8. Set D.P. switch S2
and replace unit in case.

Example 2 (Positive Offset):

PAXLPV is to be calibrated to match a flow transducer whose output is 0

V @ 40 GPM and 5 V @ 650 GPM.

READOUT SPAN (Rs) = 650 - 40 = 610
SWING VOLTAGE (Vs) = 5 V (max) - 0 V (min) = 5 V
SPAN PER VOLT (Rs/Vs) = 610 / 5 V = 122

ADJUSTMENTS

Null the unit per Steps 1 to 4 of the
calibration steps.

Set the coarse and fine span adjustments
to get a readout of 610 @ 5 V (SPAN PER
VOLT = 122) per Steps 5 and 6.

Set offset to readout 40 @ 0 V per Step 7.

Check the readout @ max. (5 V) and min.

(0 V) and fine tune (tweak) as required
per Step 8.

Example 3 (Negative Slope):

A liquid level sensor puts out 1 V when a storage tank is full and 11 V

when the tank is empty. The PAXLPV is to read out 100.0 when the tank is
full and zero when the tank is empty.

READOUT SPAN (Rs) = 1000 - 0 = 1000
SWING VOLTAGE (Vs) = 1 V (max) - 11 V (min) = -10 V
SPAN PER VOLT (Rs/Vs) = 1000 / -10 V = -100

In this case, the signal voltage is reversed [Term. 3 (+) with respect to Term.
4 (-)] causing the readout to go “down” (increasingly negative) as the
negative voltage increases (hence, the negative (-) SPAN PER VOLT).

ADJUSTMENTS

Null the unit per Steps 1 to 4 of the

calibration steps.

Set the slope of the transfer curve with the

span adjustments to get a readout of -1000
@ -10V

(SPAN PER VOLT

=

-100) per Steps 5 and 6.

Move the transfer curve up by applying (+)

offset per Step 7 until readout is +1000 @
-1 V.

Check extreme readings per Step 8 0

readout @ -11 V and +1000 @ -1 V. Set
D.P. switch S1 ON and replace unit in case.

6.0 A

PPLICATIONS

Red Lion Controls
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839

Red Lion Controls AP

Unit 101, XinAn Plaza

Building 13, No.99 Tianzhou Road

ShangHai, P.R. China 200223

Tel +86 21 6113-3688

Fax +86 21 6113-3683

Red Lion Controls BV

Printerweg 10

NL - 3821 AD Amersfoort

Tel +31 (0) 334 723 225

Fax +31 (0) 334 893 793