beautypg.com

Cub4v signal input, Voltmeter scaling, Cub4i signal input – Red Lion CUB4V User Manual

Page 3

background image

3

CUB4V SIGNAL INPUT

The voltage range is selected by setting one of the DIP switches S1 to S4 for

the desired input voltage. The unit will indicate the direct readout for the range

selected.
Note: Only one Voltage Range switch (S1-S4) should be selected (ON).

The SCALE DIP switch (S5) and the Scaling Potentiometer are used when it

is necessary to scale the display to indicate other engineering units. The Scale

switch should be left in the “OFF” position when the application requires direct

voltage readout on the display.

The Calibration Potentiometer has been set at the factory and should not be

adjusted unless the unit is being re-calibrated with an accurate voltage source.

The power supply common and signal common are connected internally at

the same screw terminal marked COMM. The power supply common, and the

signal common must be at the same voltage potential. The voltmeter cannot

measure a voltage with a reference that is different than the power supply

common.

Caution: The Maximum Voltage for each switch position must not be

exceeded or the unit may be damaged (See Specifications).

Caution: 9 to 28 VDC power circuit is not isolated from the

signal circuit.

VOLTMETER SCALING

In many industrial applications, a voltmeter is required to display a reading

in terms of PSI, RPM, or some other unit of measure. The signal voltage being

measured is normally generated by a transducer which senses the variable and

delivers a linear output voltage. To provide the desired readout at the specified

voltage, the voltmeter must be scaled. The Scale switch, when in the “ON”

position, enables the Scale Potentiometer. The Scale Potentiometer is used with

a voltage range to provide a method of scaling the unit. The voltage DIP

switches are used to select one of the four coarse Division Factor ranges and the

Scale Potentiometer is a fine scale adjustment within the selected range. The

chart below shows the division factor range associated with each range

selection switch.

DIVISION FACTOR RANGE SELECTION CHART

S1: 0-199.9 mVDC (0.1 D.F. 1.2)

S2: 0-1.999 VDC (1.2 D.F. 10.5)

S3: 0-19.99 VDC (10.5 D.F. 100.5)

S4: 0-199.9 VDC (100.5 D.F. 1300)

Note: Enabling the Scale Potentiometer does NOT affect the calibration of

the unit.
To determine the proper voltage range for an application requiring scaling,

the “Division Factor” required to provide the proper display reading must first

be determined by using the following formula.

USING THE FORMULA:

D.F = VT x D.D.P.

D.R.

WHERE:

VT

= Maximum Transducer Output

D.D.P. = Display Decimal Point

D.F.

= Division Factor

D.R.

= Desired Reading

D.D.P.

0.000 = 1

The DISPLAY DECIMAL POINT (D.D.P.)

00.00 = 10

is determined by the desired decimal

000.0 = 100

point placement in the readout.

0000 = 1000

POINTS

DECIMAL

SWITCHES

VOLTAGE

CAL. POT.

SCALE POT.

8

7

6

5

4

3

2

1

0.000

0.00

0.

0

SCAL

E

199.9VDC

19.99VDC

1.999VDC

199.9mVD

C

4

199.9VDC

YORK, PA.

RED LION CONTROLS

1 COM

3 SIG.+

1.999VDC

199.9m

V

19.99VDC

ON

2

1

3

CALIB

.

SCAL

E

0.

0

SCAL

E

0.000

0.00

MADE IN U.S.A.

6

5

7 8

D.P.

V+ 2

CUB4V

M1508F

After the Division Factor for the application has been calculated, the proper

voltage range switch that will provide for the Division Factor is set to the “ON”

position. Use the “Division Factor Range Selection Chart” to choose the proper

DIP switch setting.
Note: Only one voltage DIP switch should be turned on. Set the switch before

the voltage signal is applied.

EXAMPLE: A relative humidity transducer delivers a 7.0 VDC voltage at a

relative humidity of 75%.

D.F. = VT x D.D.P. = 7.0 x 1000 = 93.3

D.R. 75

This Division Factor is between 10.5 and 100.5, therefore DIP switch

position S3 is set to the “ON” position. The Scaling Potentiometer is then

adjusted for the desired readout at a known relative humidity.

CUB4I SIGNAL INPUT

The CUB4 Current Meter has four current ranges that are selected by

positioning the jumper in the proper location on the male header strip.

The SCALE DIP switch (S1) and the Scaling Potentiometer are used when it

is necessary to scale the display to indicate other engineering units. The Scale

switch should be left in the “OFF” position when the application requires direct

current readout on the display.

When the power supply is floating (unreferenced) to the desired measurement

points, the (-) signal input and the power supply common should be connected.

If the power supply is not floating (referenced), the common mode voltage

between the (-) signal input and power supply common terminal must not be

greater than 1.0 V peak. A common mode voltage higher than 1.0 V peak will

result in a measurement error.

The Calibration Potentiometer has been set at the factory and should not be

adjusted unless the unit is being re-calibrated with an accurate current source.

Caution: The Maximum Current for each jumper position must not

be exceeded or the unit may be damaged (See Specifications).

BLOCK DIAGRAM CUB4V

19.99m

A

199.9m

A

199.9µA

1.999m

A

CAL. POT.

SCALE POT.

4

3

2

1

0.000

0.00

0.

0

SCAL

E

YORK, PA.

RED LION CONTROLS

3 SIG.-

1 COM

1.999mA

199.9uA

SCAL

E

ON

1

0.00

0.00

0

3

0.

0

2

4

199.9mA

19.99mA

MADE IN U.S.A.

CALIB

.

SCAL

E

V+ 2

SIG.+ 4

This manual is related to the following products: