Chapter 4 ________________________________________________________________ Operation

VAISALA _______________________________________________________________________ 51

Setting, Scaling and Testing Analog Outputs

AMODE Set Analog Outputs
(0/4 ... 20 mA)

Syntax: AMODE ch1 ch2

Where

ch1 and ch2

=

I0 = 0 ... 20 mA
I1 = 4 ... 20 mA

Example:

>amode i1 i1
Ch1 output mode: 4...20mA
Ch2 output mode: 4...20mA
>

ASEL Select Parameter for Analog
Outputs

Syntax: ASEL xxx yyy

Where

xxx

=

Quantity of channel 1

yyy

=

Quantity of channel 2

Use abbreviations shown in Table 9 on page 52.