Configuring analog output, Set/show analog output mode – Vaisala HMT130 User Manual
Page 43

Chapter 4 ________________________________________________________ Serial Line Operation
VAISALA ________________________________________________________________________ 41
Configuring Analog Output
Set/Show Analog Output Mode
Use the AMODE command to show or set the analog output mode.
AMODE [CH1mode CH2mode] [CH1lowlimit CH1highlimit]
[CH2lowlimit CH2highlimit]
Where
CH1mode
CH2mode
= 0_5V (Output scale 0 … 5V)
0_10V (Output scale 0 … 10V)
X_YV (Output scale lowlimit … highlimit)
CH1lowlimit
CH2lowlimit
= Low limit for output voltage
CH1highlimit
CH2highlimit
= High limit for output voltage
Example (Channel 1 limits configured as 1 ... 6 volts and Channel 2 as
0 ... 5 volts):
>amode x_yv 0_5V 1 6
Ch1 Analog out mode : X_YV
Ch2 Analog out mode : 0_5V
Ch1 low limit : 1
Ch1 high limit : 6
>
Example (User prompted to accept currently used channel limits or enter
new limits):
>amode x_yv
Ch1 Analog out mode : X_YV
Ch2 Analog out mode : 0_10V ?
Ch1 low limit : 0 ?