Section 3 Troubleshooting

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Output phase
failure
protection

This function stops the inverter output if one of the
three phases (U, V, W) on the inverter's output side
(load side) results in open phase.

• Check the wiring

(Check the motor for a
fault.)

• Check that the capacity

of the used motor is not
smaller than the inverter
capacity.

• Wire the cables

properly.

• Check the setting of

Pr. 251 "output phase
failure protection
selection".

Fan fault

For the inverter which contains a cooling fan, FN
appears on the operation panel when the cooling fan
stops due to a fault or operates differently from the
setting of Pr. 244 "cooling fan operation selection".

Check the cooling fan for
a fault.

Change the fan.

Stall prevention
(overcurrent)

During acceleration—If a current of more than
150% of the rated inverter current flows in the motor,
this function stops the increase in frequency until the
overload current reduces to prevent the inverter from
resulting in overcurrent shut-off. When the overload
current has reduced below 150%, this function
increases the frequency again.
During constant-speed operation—If a current of
more than 150% of the rated inverter current flows in
the motor, this function lowers the frequency until the
overload current reduces to prevent overcurrent
shut-off. When the ~ overload current has reduced
below 150%, this function increases the frequency up
to the set value.
During deceleration—If a current of more than
150% of the rated inverter current flows in the motor,
this function stops the decrease in frequency until the
overload current reduces to prevent the inverter from
resulting in overcurrent shut-off. When the overload
current has reduced below 150%, this function
decreases the frequency again.

Check the motor for use
under overload.

The acceleration/
deceleration time may
change. Increase the
stall prevention
operation level with Pr.
22 "stall prevention
operation level", or
disable stall prevention
with Pr. 156 "stall
prevention operation
selection".
Note: The stall
prevention operation
current can be set as
desired. It is
factory-set to 150%.

Stall prevention
(overvoltage)

During deceleration—If the regenerative energy of
the motor increases too much to exceed the brake
capability, this function stops the decrease in
frequency to prevent overvoltage shutoff. As soon as
the regenerative energy has reduced, deceleration
resumes.

• Check for sudden speed

reduction.

• The deceleration time

may change. Increase
the deceleration time
using Pr. 8
"deceleration time"

PU stop

A stop made by pressing the

key of the PU has

been set in Pr. 75 "PU stop
selection".

• Check for a stop made

by pressing the

key of the operation
panel during external
operation.

• Perform opeartion

correctly.

This alarm appears if:
• The RES signal is on;
• You attempted to set any parameter value in the

external operation mode;

• You attempted to change the operation mode during

operation;

• You attempted to set any parameter value outside its

setting range.

• You attempted to set any parameter value during

operation (while signal STF or STR is ON).

• You attempted to set any parameter value while

parameter write is being inhibited in Pr. 77
"parameter write inhibit selection".

• Perform operation

correctly.

No Motor Operation With AC Drive Fault

(continued)

Operation
Panel
Indication

Name

Description and NOTES

Check point

Corrective action

STOP

RESET

STOP

RESET