Cooling system, Intake temp tab – HP Modular Cooling System Options User Manual
Page 22

Web interface 22
These menu options enable the Admin to configure the settings for the management module. The Setup tab
and all menu options are not available to User accounts.
Cooling System
Click Cooling System in the left navigation frame to access the Cooling System screen. This screen enables
the Admin to configure cooling system settings for the management module.
The Cooling System screen contains the following:
•
•
•
Advanced tab
•
Intake Temp tab
This screen enables the Admin to change server intake temperature settings for the management module.
To change the server intake temperature settings:
1.
Enter a server intake temperature set point in the Server Intake Temperature Set Point field.
2.
Enter a maximum air temperature at which a critical alarm is issued and a trap is sent if the server intake
temperature exceeds the value listed in the High Temperature Threshold field.
3.
Enter an air temperature at which a warning is issued and a trap is sent if the server intake temperature
exceeds the value listed in the Warning Temperature Threshold field.
4.
Enter an air temperature at which an alarm is issued and a trap is sent if the server intake temperature
drops below the value listed in the Low Temperature Threshold field.
The temperature fields specific to the Emergency Door Opening are only visible if the Emergency Door
Opening function is enabled. For more information, see Automatic Door Release ("
" on page