beautypg.com

General menu – HP Modular Cooling System Options User Manual

Page 30

background image

Web interface 30

3.

Enter a time interval in the Time Interval field.

4.

Select a timer function from the Timer Function dropdown box.

5.

Do one of the following:

o

Click Save Settings to save the information.

o

Click Cancel to undo the changes.

General menu

Click General in the left navigation frame to display the General screen. This screen enables the Admin to

configure general management module parameters.

To change the general parameters:

1.

Enter a date in the Date field. (If NTP is enabled in the Network menu, do not enter a date in this field.)

2.

Enter a time in the Time field. (If NTP is enabled in the Network menu, do not enter a date in this field.)

3.

Select a date format from the Date Format dropdown box. Use MM/DD/YYYY for U.S. date format and
DD.MM.YYYY for Euro/World format.

4.

Select a temperature unit from the Temperature Units dropdown box.

5.

Select a measurement unit from the Measurement Units dropdown box.

6.

Select to enable or disable the audible alarm from the Audible Alarm (Beeper) radio buttons.

o

Select Enable to allow the audible alarm to sound when an alarm is generated.

o

Select Disable to not allow the audible alarm to sound when an alarm is generated.

7.

Select to enable or disable the reset alarm relay function in the Alarms/Warnings tab (on page

26

),

using the Alarm Relay Options radio buttons.

o

Select Enable to allow the alarm relay function when an alarm is generated.

o

Select Disable to not allow the alarm relay function when an alarm is generated.

8.

Select to close, open, or turn off the alarm relay options from the Alarm Relay Options radio buttons.

o

Select Close so that the alarm relay disconnects a circuit (normally closed) upon alarm activation.

o

Select Open so that the alarm relay completes a circuit (normally open) upon alarm activation.

This manual is related to the following products: