Timers tab – HP Modular Cooling System Options User Manual
Page 29
Web interface 29
To test the Automatic Door Release feature:
1.
At the bottom of the screen, click the Door Opening Test button. A new screen appears.
2.
Choose one of the following:
o
To begin the test and open the rack doors, click OK.
o
To return to the Advanced screen, click Quit.
NOTE:
To avoid an increase in relative humidity, after completing the Door Opening test, be
sure the doors are closed. To verify that the doors are closed, go to the Home screen.
NOTE:
You can also perform this test from the Operator Display.
Timers tab
This screen enables the Admin to change timer settings for the management module. Timers are used to
disable particular trap receivers on different days at different times of the week.
To change the timer settings:
1.
Select to enable or disable the timer control from the Timer Control radio buttons.
2.
Select a day of the week from the Day of Week dropdown box.