beautypg.com

HP Modular Cooling System Options User Manual

Page 44

background image

Cooling performance parameter settings 44

IMPORTANT:

Temperature Control Manual mode is for service and troubleshooting only and is

not to be used in a production environment.

Parameter

Function

Temperature
Control

Used in Auto mode to determine if the MCS 5042 unit

operates in Auto mode or Manual mode

Fan Speed Target Used in Manual mode to increase or decrease the fan

speed

Water Valve

Used in Manual mode to vary the opening percentage of

the water valve in Manual mode

Delta Temperature
for Minimum Fan

Speed

Used in Auto mode to set the maximum delta temperature
when the Minimum Fan Speed will be used

Delta Temperature
for Maximum Fan

Speed

Used in Auto mode to set the minimum delta temperature

when the Maximum Fan Speed will be used

Cooling Liquid
Heat Capacity

(Cw) Value

Used in Auto mode to calculate the energy extracted by

the air to water heat exchanger unit (This value for pure

water is 4,187 Ws/kgK and can be a lower value if
additives are included in the water.)

Dewpoint
Monitoring

Used in Auto mode to determine if the inlet water

temperature is below the dew point, which might result in
excessive condensation

Delta temperature (Server Intake Temp/Server Exhaust Temp)

Delta temperature is calculated from the temperature difference between the server intake temperature and

server exhaust temperature. The server intake temperature, or cold air, is the air coming from the heat

exchanger unit and pushed through the fan units. The server exhaust temperature, or hot air, is the air coming
from the fan units and being pushed through the heat exchanger unit.
Example

Server intake
temperature

Server exhaust
temperature

Top

24.5°C (76.1°F)

38.8°C (101.8°F)

Middle

24.8°C (76.6°F)

39.1°C (102.4°F)

Bottom

25.1°C (77.2°F)

40.3°C (104.5°F)

Average

24.8°C (76.6°F)

39.4°C (102.9°F)

Adjusting the cooling air flow provided by the MCS unit

To adjust the cooling air flow provided by the MCS unit while in Temperature Control Auto mode:

1.

Click the Setup tab (on page

21

).

2.

Click the Advanced tab.

3.

Enter a Delta Temperature For Minimum Fan Speed.

4.

Enter a Delta Temperature For Maximum Fan Speed.

This manual is related to the following products: