Royal Series Water Temperature Control Units

Make sure that the high limit on the controller is set to the values
listed in the following table, based on the switch adjustment. This
prevents the pump from cavitating and damaging the seal, the
switch, and heater element(s).

psig

kPa

Max. temp. ºF

Max. temp. ºC

5 psig

34.4 kPa

227ºF

108ºC

10 psig

68.9 kPa

240ºF

116ºC

15 psig

103.4 kPa

250ºF

121ºC

Safety Thermostat

Disconnect main power. Open the electrical enclosure and
disconnect the neutral lead on the safety thermostat from the
terminal strip. Protect the stripped lead to prevent short circuits.
Close the enclosure, reconnect main power, and push the

START

button. The heater should not turn on and the

Over Temperature

indicator should illuminate. Disconnect main power before
reconnecting the thermostat lead
.


6-6 Cleaning and Storage

Inspect the unit daily for leaks. Wipe down the unit

periodically to remove dirt and dust buildup, especially the
motor casing.

• Drain and flush the unit every six (6) months to remove

sediment buildup.

• Completely drain the unit and carefully blow out the piping

with pressurized air before placing the unit in storage.