Make sure that the high limit on the controller is set to the values
listed in the following table, based on the switch adjustment. This
prevents the pump from cavitating and damaging the seal, the
switch, and heater element(s).
psig
kPa
Max. temp. ºF
Max. temp. ºC
5 psig
34.4 kPa
227ºF
108ºC
10 psig
68.9 kPa
240ºF
116ºC
15 psig
103.4 kPa
250ºF
121ºC
Safety Thermostat
Disconnect main power. Open the electrical enclosure and
disconnect the neutral lead on the safety thermostat from the
terminal strip. Protect the stripped lead to prevent short circuits.
Close the enclosure, reconnect main power, and push the
START
button. The heater should not turn on and the
Over Temperature
indicator should illuminate. Disconnect main power before
reconnecting the thermostat lead.
6-6 Cleaning and Storage
• Inspect the unit daily for leaks. Wipe down the unit
periodically to remove dirt and dust buildup, especially the
motor casing.
• Drain and flush the unit every six (6) months to remove
sediment buildup.
• Completely drain the unit and carefully blow out the piping
with pressurized air before placing the unit in storage.