beautypg.com

Figure 3 royal series unit full-load amps – Sterlco Royal Series Compact Temperature Control Unit User Manual

Page 11

background image

Royal Series Water Temperature Control Units

Page 11

Figure 2

Typical Royal Upright Series Water Temperature Control Unit and Specifications

48"

3 3/4"

28"

13"

Model

Dimensions

Shipping

number Pump

H W

D

weight

460 230 letter hp kW

gpm

lpm

psig

kPa

in.

cm in. cm in. cm lbs.

Kg

C ¾

0.56

30

113.6

25

172.4

D 1 0.75

35

132.5

30

206.9

F 2 1.50

50

189.3

30

206.9

G 3

2.24

60

227.1

35

241.3

210

96

H 5 3.73

75

283.9

54

372.3

J 7½ 5.60

90

340.7

63

434.4

240

109

2012,

9 kW heater

K 10

7.46

120

454.2

55

379.2

48

122

13 33 28 71.1

270

123

Figure 3

Royal Series Unit Full-Load Amps

Model

Full-load amps at 460 volts

hp

kW

9 kW heater

12 kW heater

18 kW heater

24 kW heater

36 kW heater 48 kW heater

0.75 hp 0.56 kW

12.7 amps

16.5 amps

24.0 amps

31.6 amps

47.4 amps

62.4 amps

1.00 hp 0.75 kW

13.1 amps

16.9 amps

24.4 amps

32.0 amps

47.8 amps

62.8 amps

2.00 hp 1.50 kW

14.7 amps

18.5 amps

26.0 amps

33.6 amps

49.4 amps

64.4 amps

3.00 hp 2.24 kW

16.1 amps

19.9 amps

27.4 amps

35.0 amps

50.8 amps

65.8 amps

5.00 hp 3.73 kW

18.9 amps

22.7 amps

30.2 amps

37.8 amps

56.6 amps

71.6 amps

7.50 hp 5.60 kW

22.3 amps

26.1 amps

33.6 amps

41.2 amps

57.0 amps

72.0 amps

10.00 hp 7.46 kW

26.0 amps

30.0 amps

37.0 amps

45.0 amps

60.0 amps

75.0 amps

49

7

/

8