beautypg.com

5 checking motor rotation direction, 6 shutting down the temperature control unit – Sterlco Royal Series Compact Temperature Control Unit User Manual

Page 36

background image

Page 36

Royal Series Water Temperature Control Units

TCU systems provide temperature control on processes by

directly heating the process water and injecting cooling water
into the process water.

When the unit is energized, the pump starts and a one minute

vent sequence opens the cooling/vent valve to remove any air
trapped in the process piping.

If the cooling water supply pressure is insufficient, the low

cooling water pressure cutout switch (set at 16 psig, 10 psig
differential [110.32 kPa/1.10 bars, 68.95 kPa/0.69 bars
differential]) opens, the

LOW WATER PRESSURE

indicator

lights, and the unit does not operate until the pressure is 16 psig
(110.32 kPa/1.10 bars) or more. You need at least 16 psig
(110.32 kPa/1.10 bars) for the best cooling capacity and to
prevent water boiling in the process circuit at high
temperatures, particularly at the pump suction.

After venting, the microprocessor controller monitors the

TO

PROCESS

RTD probe, cycling open the cooling/vent valve to

discharge warm water or energizing the immersion heater to
maintain the process set temperature.

5-5 Checking Motor Rotation Direction

Check for correct pump rotation direction by looking at the top of
the motor. Press the

START

button and the

STOP

button, and note

the direction that the motor turns. Rotation should be clockwise
when viewed from the motor end.

Note: Make sure that a qualified electrician performs the

following steps.

To change rotation direction:

1.

Disconnect and lock out power at the fused disconnect.

2.

Reverse any two incoming leads at the power terminal
blocks.

3.

Do not switch leads at the motor or motor starters.

5-6 Shutting Down the Temperature Control Unit

Cool the unit down by selecting a set point of zero (

0

). Let the

unit stabilize at one temperature close to the incoming water
temperature, then press the

STOP

button. Now press the

VENT

button to relieve any remaining pressure in the system.

This manual is related to the following products: