Royal Series Water Temperature Control Units
Page 25
Bring properly sized power leads and ground from a fused
disconnect (installed by your electrician) to the unit. Provide
external overcurrent protection to the unit, using circuit breakers or
fuses. If you use fuses, make sure that they are dual-element time-
delay fuses, sized according to your electrical code. Make sure that
all electrical connections are tight.
Important!
1. Electrical connections must comply with all applicable electrical codes.
2. The temperature control unit must be grounded in accordance with NEC
Article 250.
3. Voltage must be within plus or minus ten percent (
±10%) of the nameplate
rating.
4. Make sure your installer provides external protection.