Royal Series Water Temperature Control Units

FROM PROCESS — 1½” NPT

Water from the process re-enters the Royal Series system to be
tempered and re-circulated back into the process.

3-8 Making Cooling Water Connections

WATER IN — ¾”

The cooling water supply inlet from a cooling tower, a chiller, or a
city water supply.


!

CAUTION

If a non-relieving device such as a regulator, ball valve,

or check valve is installed on the WATER IN line,

you MUST install an expansion tank

of at least ½ gallon (about 2 liters) capacity.

Failure to do so can result in system overpressure from thermal expansion.

Install the tank configured as shown below:

Royal Series

unit

Expansion

tank

Non-relieving

device

Check the expansion tank frequently to make sure it is not flooded.