ROTRONIC HF65 User Manual
Page 28
![background image](/manuals/373296/28/background.png)
E-M-HF63_65-V1_11
Rotronic AG
Bassersdorf, Switzerland
Document code
Unit
Instruction Manual
Document Type
HygroFlex HF63/HF65 Humidity Temperature
Transmitters: User Guide
Document title
Page 28 of 34
© 2008; Rotronic AG E-M-HF63_65-V1_11
Start-up time and data refresh rate
HF63
HF65
Start-up time
1.9s (typical) 1.9s
(typical)
Data refresh rate
1.7s (typical) 1.7s
(typical)
Configurable analog outputs
HF63
Output 1
Can be made to correspond to any parameter
Factory default parameter
Relative humidity or dew / frost point
Factory default scale
As per ordering code
Output 2
Can be made to correspond to any parameter
Factory default parameter
Temperature
Factory default scale
As per ordering code
Output 1 and Output 2
Signal type (user configurable)
0…20 mA
4… 20 mA
0… 1 V
0… 5 V
0… 10 V
User configurable scaling limits
-999.99 … +9999.99 engineering units
Maximum offset at bottom of
signal range
0…1V signal range
: 3 mV
0…5 V signal range
: 50mV
0…10 V signal range
: 90mV
0…20 mA signal range : 4uA
4…20 mA signal range : no offset
Short circuit tolerant
Yes
Maximum external load
500 Ω (current output)
Minimum external load
1 kΩ (0…1 V output)
5 kΩ (0…5 V output)
10 kΩ (0…10 V output)
0 Ω (current output)
Digital interface
HF65
Interface type
RS-485 or USB + RS-485 or Ethernet (TCP/IP) wired or wireless +RS-485
Can be configured for use with a Modbus BUS system
Service connector
HF63
HF65
Interface type
UART
Maximum service cable length
5 m (16.4 ft)
General specifications
HF63
HF65
Optional display
LC, 1 or 2 decimals resolution, backlight, trend and alarm indication
Probe material
Polycarbonate
Probe dust filter material
Depends on filter type
Housing material
ABS
Housing protection grade
IP 65 (except HF55 – USB or Ethernet)
Physical dimensions
See Models
Weight
300 g (10.6 oz)
300 g (10.6 oz)