EtherNet/IP Bus module
– Supplementary manual options for NORD - Frequency Inverters
30
BU 2100 GB-2213
Error
Meaning
Remarks
1000
EEPROM error
EMC fault, module defective
1020
Timeout
via P151/P513 monitoring
1030
System bus BUS OFF
No 24V supply to the bus, connections not correct
5501
DIP switch error
The DIP switches (IP address) could not be read correctly
5600 …
5609
Internal error
Module not ready
5610
General network error
5611
Ethernet Watchdog timeout
5612
Bus cable fault
Bus cable connection interrupted
5613
IP address error
IP address of the module has been doubly assigned
5640
MAC address error
Errors which occur in relation to the module are depicted as follows in the error memory of the
frequency inverter (P700 / P701).
Error
(E010)
Meaning
Remarks
10.0
Connection error
Contact to SK xU4 lost
10.1
ASIC errors
Communication to EtherNet/IP - ASIC lost
•
Switch-off of the supply voltage
10.2
Ethernet/IP Watchdog timeout
Telegram transfer error
•
Check the connections and links, program sequence and
Bus Master
10.3
Timeout by P151/P513
Telegram transfer error
•
Check the connections and links
•
Check the Watchdog time
10.4
IP address error
IP address of the module has been doubly assigned
10.5
Internal error
Module not ready
10.6
Bus cable fault
Bus cable connection interrupted
10.8
The connection between the inverter
and the module had a timeout
Only SK TU3 module
10.9
The connection between the inverter
and the module had a timeout
Only SK xU4 module