Module status, Status of digital input, Relay status – NORD Drivesystems BU2100 User Manual
Page 26
EtherNet/IP Bus module
– Supplementary manual options for NORD - Frequency Inverters
26
BU 2100 GB-2213
P173
Module Status
(Module status)
SK
EB…
SK TU3-
…
SK xU4-
…
16 bit
0 ... 0xFFFF
Operating status of the module.
Bit 0 =
Module ready for operation*
Bit 1 =
Cyclic communication*
Bit 2 =
Timeout by Ethernet bus*
Bit 3 =
Timeout (P151/P513)*
Bit 4 =
No communication with ASIC*
Bit 5 =
General configuration error*
Bit 6 =
System bus "BUS Warning"**
Bit 7 =
System bus "BUS OFF"**
Bit 8 =
FI 1 status
Bit 9 =
FI 1 status
Bit 10 =
FI 2 status**
Bit 11 =
FI 2 status**
Bit 12 =
FI 3 status**
Bit 13 =
FI 3 status**
Bit 14 =
FI 4 status**
Bit 15 =
FI 4 status**
* Except for ...IOE modules
** Except for SK TU3 versions
THe status of the frequency inverter is determined from a High bit and a Low bit: e.g. FI
1: High bit: Bit 9; low Bit: Bit 8
High Bit
Low Bit
Meaning
0
0
FI is offline
0
1
FI is not supported
1
0
FI is online
1
1
Bus error (PDO or SDO monitoring)
P174
Status of digital input
(Status of the digital inputs)
SK
EB…
SK xU4-
…
8 bit
0 ... 0xFF
Image of the switching status of the digital inputs of the module.
Bit 0 =
Digital input 1
Bit 1 =
Digital input 2
Bit 2 =
Digital input 3*
Bit 3 =
Digital input 4*
Bit 4 =
Digital input 5**
Bit 5 =
Digital input 6**
Bit 6 =
Digital input 7**
Bit 7 =
Digital input 8**
* Except for ... CU4- modules
** Only SK TU4-ECT, SK TU4-EIP, SK TU4-PNT and SK TU4-POL
P175
Relay Status
(Switching status of relay)
SK
EB…
SK TU4-
…
8 bit
0 ... 3
Image of the switching status of the relay outputs of the module.
Bit 0 =
Relay 1
Bit 1 =
Relay 2