5 Parameter

BU 2100 GB-2213

29

Para-
meter

Parameter name

Recommended setting

Remarks

SK 5xxE

SK

180E … SK 2xxE

P545

Actual BUS value 3

According to the
function:

Not available

Only SK

500E … 535E

P546

Function Setpoint BUS
value

According to the
function:

According

to

the

function:

SK 54xE and SK

180E …

SK 2xxE: up to 5 setpoints
each

P547

Function BUS setpoint
2

According to the
function:

Not available

Only SK

500E … 535E

P548

Function BUS setpoint
3

According to the
function:

Not available

Only SK

500E … 535E

Info parameters

P700

Present

Operating

status

Fault / Warnings / Reason for
starting disabled condition

P701

Last fault

P740

Process data BUS In

P741

Process data BUS Out

P742

Data base version

P744

Configuration

Not relevant

P745

Module version

Not available

P746

Module status

Not available

Possible values

Bit

Meaning

0

Module initialised

1

Cyclical communication

2

Vacant

3

Vacant

4

Error 1

5

Error 2

6

Error 3

7

Vacant

8-15

Module number
EtherNet/IP = 23


Table of Errors

Error

Meaning

3

2

1

0

0

0

No error

0

0

1

No communication
with ASIC

0

1

0

Bus Timeout

0

1

1

P513 timeout

1

0

0

IP already assigned

1

0

1

General config. error

1

1

0

No Ethernet cable

1

1

1

Communication error


P748

CANopen status

Not relevant for
SK TU3 modules

System bus status

Error messages

Error messages from the module - present errors or archived messages relating to the last error - can
be read out via the module parameter (P170). The error messages are lost if the module is switched
off.