4.1.1 Control word (STW)
The control word (STW) is the first word transferred to the frequency inverter in the process data area
in an order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
(hex)
. In
general the command "Standby" should be the first command which is transferred to the inverter.
Bit
Valu
e
Meaning
Remarks
0
0
Not ready for operation
Reverse with the brake ramp, with disconnection from supply at f=0Hz (OFF1)
1
Ready for operation
Frequency inverter ready for operation
1
0
Disable voltage
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled. (OFF2)
1
Do not disable voltage
Operating condition OFF 2 is cancelled
2
0
Emergency Stop active
Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition (OFF3).
1
Emergency
Stop
not
active
Operating condition OFF 3 is cancelled
3
0
Disable operation
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.
1
Enable operation
The output voltage is enabled; ramp to the existing setpoint
4
0
Pulse not enabled
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains
in the operation enabled state.
1
Enable pulses
Enable ramp generator
5
0
Ramp not enabled
The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).
1
Enable ramp
Enable setpoint on ramp generator
6
0
Setpoint not enabled
Selected setpoint value is set to zero on the ramp generator.
1
Enable setpoint
Selected ramp generator setpoint is activated.
7
0
No acknowledgement
With the switch from 0 to 1, errors which are no longer active are acknowledged.
1
Acknowledge
error
(01)
Note: If a digital input has been programmed for the "ack.fault" function, this bit
must not permanently be set to 1 via the bus (otherwise, flank evaluation would
be prevented).
8
0
1
Start function 480, 11
Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For further
details of the function please refer to parameter P480.
9
0
1
Start function 480, 12
Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For further
details of the function please refer to parameter P480.
10
0
Control data invalid
The transmitted process data is invalid.
1
Control data valid
Valid process data is transferred from the master.
Note: In order for the transmitted setpoint to be valid, this bit must also be set
(setting: interface), even if only setpoint values are transmitted via the bus.
11
0
1
Rotation right is on
Rotational direction right (priority) ON*
12
0
1
Rotation left is on
Rotational direction left ON*
13
0/1
Reserved
Reserved
14
0/1
Parameter set Bit 0 ON
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Parameter set Bit 1 ON
* If Bit 12=0, then "Direction of rotation right ON" applies
Table 3: Control word (STW)
4.1.2 Status word (ZSW)
In the inverter response telegram, in the area of the process data the status word (ZSW) is transferred
as the first word. The meaning of the individual bits deviate for some types of devices.