4.1.4 Setpoint (SW) and Actual Value (IW)

The functions of the setpoint and the actual value are assigned via frequency inverter parameters:

Type

Relevant parameter

Setpoint

P546 … P548

Actual value

P543 … P545

The following three kinds of data transfer are possible:

Percentage transfer

The process value is transferred as an integer with a value range of -32768 to 32767 (8000 hex to
7FFF hex). The value 16384 (4000 HEX) corresponds to 100 %. The value -16384 (C000 hex) is
equal to -100 %.

For frequencies, the 100 % value corresponds to the FI parameter "Maximum Frequency" (P105) and
for currents, this is the FI parameter "Torque Current Limit" (P112) Frequencies and currents result
from the following formulae.

16384

105

P

Value

Frequency

16384

112

P

Value

Current

"Value" represents the 16Bit actual or setpoint value transmitted via the bus

Binary transmission

Inputs and outputs, as well as Digital In bits and Bus Out bits are processed bit-by-bit.

Transmission of positions

In the FI, positions have a value range of +/- 50000.000 rotations. A motor rotation can be divided into
a maximum of 1000 steps. This scaling is independent of the encoder which is used.

The 32 Bit value range is divided into a Low word and a High word, so that 2 setpoints or actual values
are required for the transfer. It does not matter which 2 words (except for the 1st word) are used for
this.

Direction of

transmission

Transmitted data (12 Byte)

1st word

2nd word

3rd word

4th word

5th word

6th word

Busmaster

bus module

Control word

32 bit setpoint

Setpoint 3

Setpoint 4

Setpoint 5

Busmaster

bus module

Status word

Actual value
1

32 bit actual value

Actual value
4

Actual value
5

Table 5: Depiction of 32Bit setpoint/actual values

It is also possible to only transmit the Low component of the position. This results in a limited value
range from +32,767 to -32,768 rotations. This value range can be extended with the aid of the gear
ratio factor (P607 & P608). However, it must be noted that there is an according reduction in the
resolution.

4.1.5 Example: "Switch on and off + setpoint"

In this example, a frequency inverter is controlled with a setpoint (setpoint frequency). The frequency
inverter responds with an actual value (actual frequency). The "maximum frequency" is parameterised
to 50 Hz.

Relevant parameters: