Specific bus parameters (p16x), P152 factory setting, Min. system bus cycle – NORD Drivesystems BU2100 User Manual
Page 22: Tb-io access, Ip address
EtherNet/IP Bus module
– Supplementary manual options for NORD - Frequency Inverters
22
BU 2100 GB-2213
P152
Factory Setting
(Load factory settings)
SK TU3-
…
SK xU4-
…
8 bit
0 ... 1
{ 0 }
With the selection of the relevant value anc confirmation with the OK key, the selected parameter
range is set to the factory setting. Once the setting has been made, the value of the parameter
automatically returns to 0.
0 = No change: Does not change the parameterisation.
1 = Loading the factory settings: The complete parameterisation of the FI reverts to the
factory setting. All originally parameterised data are lost.
P153
... [-01]
... [-02]
Min. System Bus Cycle
(Minimum cycle time of system bus)
SK
EB…
SK xU4-
…
16 bit
0 ... 250.00 ms
{ [-01] = 10 }
{ [-02] = 5 }
In order to reduce the bus load on the system bus, the transmission cycle time of the Service
Data Objects and Process Data Objects can be extended.
[-01] = SDO Inhibit Time
[-02] = PDO Inhibit Time
P154
... [-01]
... [-02]
TB-IO Access
(Access to technology unit IOs)
SK xU4-
…
8 bit
0 ... 5
{ [-01] = 0 }
{ [-02] = 0 }
Assignment of the writing and reading rights of the connected frequency inverter to the inputs and
outputs of the technology unit.
[-01] = Inputs
[-02] = Outputs
0 =
OFF, no effect
1 =
Broadcast, all FIs read the inputs
2 =
FI 1, reads and writes to the IOs
3 =
FI 2, reads and writes to the IOs
4 =
FI 3, reads and writes to the IOs
5 =
FI 4, reads and writes to the IOs
Specific Bus Parameters (P16x)
Parameter
{Factory seting}
Setting value / Description / Note
Device
Type
P160
... [-01]
…
... [-04]
IP Address
(IP Address)
SK TU3-EIP
SK xU4-EIP
8 bit
0 ... 255
{ [-01] = 192 }
{ [-02] = 168 }
{ [-03] = 1 }
{ [-04] = 0 }
Parameterised IP address consisting of four bytes.
The settings are only adopted after a restart of the module.
[-01] = IP High (NET-ID)
[-02] = IP (NET-ID)
[-03] = IP (NET-ID)
[-04] = IP Lo (Host)
Information
IP Lo (Host)
A value "0" in array [-04] means that the setting for this array has been made with the module
DIP switches.