3 frequency inverter status machine, Frequency inverter status machine, Table 4: status word (zsw) – NORD Drivesystems BU2100 User Manual
Page 13: 4 communication and protocol
4 Communication and Protocol
BU 2100 GB-2213
13
Bit
Valu
e
Meaning
Remarks
0
0
Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1
0
Not ready for operation
Causes: No command has been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated
1
Ready for operation
ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION
2
0
Operation not enabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3
0
No error
1
Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged
4
0
Voltage not enabled
OFF2 command applied
1
Voltage enabled
5
0
Emergency stop
OFF3 command applied
1
No emergency stop
6
0
Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7
0
No warning
1
Warning active
Drive operation continues, no acknowledgement necessary
8
0
Setpoint not reached
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
1
Setpoint reached
Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)
9
0
Bus control not active
Guidance on local device has been activated
1
Bus controller active
The master has been requested to assume guidance.
10
0
1
Start function 481.9
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.
11
0
1
Rotation right is on
Inverter output voltage is turning right
12
0
1
Rotation left is on
Inverter output voltage is turning left
13
0
1
Start function 481.10
Bus bit 13 from the status word is set. For further details of function, please refer
to parameter P481.
14
0/1
Parameter set Bit 0 ON
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Parameter set Bit 1 ON
Table 4: Status word (ZSW)
4.1.3 Frequency inverter status machine
The frequency inverter passes through a status machine. The changes between various states are
triggered by the respective control commands in the process data control word. The actual status is
returned in the process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command.
The controller must check the answers from the slaves as to whether the control command has been
carried out.
The following bits indicate the status of the frequency inverter: