Appendix ii – default values, F - ufm, 11 appendix ii – default values – Dwyer UFM User Manual
Page 26
F - UFM
Issue 1.4
Page 26
Storage temperature
14°F to 140 °F (-10°C to 60°C)
Humidity
90% RH at 122°F Max
Display
LCD
2 line x 16 characters
Viewing angle
Min 30°, Max 40°
Active area
3.27 inches (W) x 0.74 inches(H)
Keypad
Format
4 key tactile feedback membrane keypad
11
Appendix II – Default values
The settings will be configured at the factory for either metric or imperial units. Table 2 lists
the metric default values.
Table 2 System Default Values
Parameter
Default Value
Dimensions
mm
Flow Rate
l/min
Pipe size
50 (mm)
4-20 mA
On, 4-20 mA selected
Flow at Max Current Equivalent to 2m/s
Flow at Min Current 0
Pulse Output
On
Volume per Pulse
10 liters
Pulse Width
25 ms
Damping
20 seconds
Calibration Factor
1.000
Zero Cut-off
0.10 m/s
Zero Offset
0.000 l/min
Table 3 lists the default values when Imperial dimensions are selected.
Table 3 System Default Values
Parameter
Default Value
Dimensions
inches
Flow Rate
USgal/min
Pipe size
2 (inches)
4-20 mA
On, 4-20 mA selected
Flow at Max Current Equivalent to 6.5 ft/s
Flow at Min Current 0
Pulse Output
On
Volume per Pulse
10 US gallons
Pulse Width
25 ms
Damping
20 seconds
Calibration Factor
1.000
Zero Cut-off
0.10 m/s ( 0.3 ft/s)
Zero Offset
0.000 gal/min