Warning, Flex-pro 5.1 wiring terminals and i/o schematics, Page 9 – Blue-White FLEX-PRO A2 ProSeries Peristaltic Pump User Manual

Page 9: T2 t4 t1, Power, Output input p1

background image

Risk of electric shock – cord connected models are supplied with a grounding
conductor and grounding-type attachment plug. To reduce risk of electric shock, be
certain that it is connected only to a properly grounded, grounding-type receptacle.

Electrical connections and grounding (earthing) must conform to local wiring codes. Be
certain that a grounding conductor is connected to terminal T11-1 located in wiring
compartment.

Risk of electric shock - Disconnect electricity before removing wiring compartment
cover.

WARNING

T1

1

3

PLS

4

4-20

(+)

2

Motor Active

(-)

5

+

-

ACTIVE 4-20mA

TRANSMITTER

SOURCE

GND (-)

4-20(+)

INPUT:
4-20 mA

INPUT:
FREQUENCY, AC
SINE WAVE, TTL,
CMOS

FUNCTION

TERM

PIN #

RATING

ELECTRICAL SP.

BLOCK DIAGRAM

T1

T1

T1

T1

T4

T4

T4

1

3

3

4

3

4

5

(+) POSITIVE

SIGNAL

(-) NEGATIVE

OUTPUT:
4-20 mA

OUTPUT:
RELAY, 3 AMP

OUTPUT:
OPEN COLLECTOR

MOTOR ACTIVE

T6

T6

2

1

(+) POSITIVE

(-) NEGATIVE

T7

1

T7

T7

2

3

120 OHM
IMPEDANCE, NON
POWERED LOOP

6 TO 30 VOLT DC
1 AMP MAX.

120 OHM
RESISTANCE
ACTIVE LOOP

Form C
3 AMP MAX AT
250 VAC,
3 AMP MAX AT
30 VOLT DC

0-1000 HZ MAX.

NO VOLTAGE

(+)

(-)

NO

C

NC

SWITCH LOAD

3 AMP MAX @ 250V AC

3 AMP MAX @ 30V DC

EXTERNAL DEVICE

6 TO 30V DC

OPEN CIRCUIT

IMPEDANCE MUST

BE GREATER THAN

50K OHM

4-20mA RECEIVER

600 OHM LOAD MAX.

(+)

(-)

Risk of electric shock - All
wiring must be insulated
and rated 300V minimum.

Terminals T1 Thru T8
Plug type
16 - 24 AWG

Power Input Terminal T11
Plug type
14 - 30 AWG

Single or dual pump (series) input.
Loop voltage must not exceed 24 Volts.

Page 9

Flex-Pro

5.1

Wiring Terminals and I/O Schematics

115V

FUSE 5A SLOW

BLOW (20 X 5MM)

POWER

T11

GROUND

N EUTRAL

(COMMON)

LINE

(HOT)

1

2

3

S1

OUTPUT

INPUT

P1

TO COM

BOARD

T7

RELAY

OUT

T3

REMOTE
IN

T2

T4

T1

FVS

3

1
2

DRY

RMT

COM

4-20mA

1 2 3

N.C. COM N.O.

1 2

(-)

(+)

1

3

PLS

4

4-20

(+)

1

2

(-)

(+)

3
4

5

(+)

(-)

SIG

DIR

T6

RS-232

T12

POWER

F1

2

Motor Active

(-)

5

T1

1

3

PLS

4

4-20

(+)

2

Motor Active

(-)

5

+

-

FREQUENCY

TRANSMITTER

SOURCE

GND (-)
PULSE

T4

FVS

3
4

5

(+)

(-)

SIG

BLUE-WHITE

FVS SENSOR

GND (-)

SIGNAL

PWR (+)

RED (+)

BLACK (-)

BARE

T3

REMOTE
IN

3

1
2

DRY

RMT

COM

T3

T3

1

2

(+) POSITIVE

(-) NEGATIVE

T3

T3

2

3

(+) POSITIVE

(-) NEGATIVE

T3

REMOTE
IN

3

1
2

DRY

RMT

COM

T4

T4

4

5

SIGNAL

(-) NEGATIVE

T4

FVS

3
4

5

(+)

(-)

SIG

BLUE-WHITE

MICRO-FLO

FLOWMETER

PULSE OUTPUT

GND (-)

SIGNAL

PWR (+)

NEGATIVE (-)

SIGNAL

1 2

(-)

(+)

T6

T7

RELAY

OUT

1 2 3

N.C. COM N.O.

(-)

(+)

T1

1

3

PLS

4

4-20

(+)

2

Motor Active

(-)

5

GND (-)

T1

T1

2

3

CLOSED WHILE MOTOR
IS ENERGIZED

NEGATIVE (-)

SIGNAL OUT

4.7K OHM

MOTOR

ACTIVE

5 TO 24 VDC

INPUT:
POWER

T11

1

T11

T11

2

3

T11

GROUND

N EUTRAL

(COMMON)

LINE

(HOT)

1

2

3

POWER

AC

VOLTAGE

115V OR 230V AC
MANUAL SWITCH
50 / 60 HZ
100W

GROUND

NEUTRAL

LINE (HOT)

115V

POWER

S1

POWER
VOLTAGE
SWITCH

SWITCH

FROM

115V TO 230V

FUSE

F1

N/A

5 AMP

5A SLOW BLOW
(20 X 5MM)

(+) POSITIVE

(-) NEGATIVE

(-) NEGATIVE

(+) POSITIVE

INPUT:
FVS SYSTEM
(FLOW VERIFICATION
SENSOR)
FS or FP MICRO-FLO
FLOW METER ONLY

INPUT:
FVS SYSTEM
(FLOW VERIFICATION
SENSOR)
FV SENSOR ONLY

INPUT:
REMOTE
START / STOP
(DRY CONTACT C.)

INPUT:
REMOTE
START / STOP
(WET CONTACT C.)

NORM. CLOSED

NORM. OPEN

COMMON

4-20

COMMON

SIGNAL