Flex-Pro
Available on certain models.
Sends a configurable 4-20 mA signal, based on pump rotor speed, to an external device. This feature can be
used to control other pumps (in sync / proportionally), data logging systems, and other external devices for plant
automation.
Default setting: Minimum Speed = 4 mA signal output
Maximum Speed = 20 mA signal output
Set to NO = disabled
Set to Yes = enabled
Time-out - Flex-Pro pumps have a time-out setting of 20 seconds while in configuration menus. If built-in timer exceeds 20 seconds
without a button being pressed, then pump will exit configuration menu. Changes will only be saved after RIGHT arrow button is
pressed and released.
Step 1
Press and release STOP button
Note: Mode cannot be changed while pump is in running.
Press and release SELECT RUN MODE button multiple
times until Mode 0 is selected.
Step 2
With Mode 0 selected, press and hold SELECT RUN MODE
button until ‘Remote’ icon begins flashing.
This indicates that you’ve entered Setup menu.
Step 3
Press and release RIGHT arrow to scroll through menu until
you see 4-20 mA icon.
To select Yes, press and release DOWN arrow.
To select No, press and release UP arrow.
To begin configuring values, select Yes.
Then press and release RIGHT arrow.
Step 4
Minimum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
Mode 0
SEt
0
yes
0
Mode 0
no
0
REMOTE
Remote
Icon
Mode 0
M
A
OUT
4-20 mA Icon
Mode 0
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump Motor Speed (%)
Milliamp Output (mA) Signal
Default Setting
0.1
0
M
A
OUT
4-20 mA Icon
SPEED
MIN
7.3
Mode 0 - Set 4-20mA Output