beautypg.com

Blue-White FLEX-PRO A2 ProSeries Peristaltic Pump User Manual

Page 12

background image

Page 12

Flex-Pro

Used to remotely start and stop pump using a dry contact closure signal.
When activated; CLOSE = START and OPEN = STOP.

Set to NO = Remote Start / Stop is disabled
Set to Yes = Remote Start / Stop is enabled

Can be used with external foot pedal, PLC, contact closure or other similar external devices.

Default setting = No (disabled)

Step 1

Press and release STOP button

Note: Mode cannot be changed while pump is in running.

Press and release SELECT RUN MODE button multiple
times until Mode 0 is selected.

Step 2

With Mode 0 selected, press and hold SELECT RUN MODE
button until ‘Remote’ icon begins flashing.
Default setting ‘NO’ will also be visible when entering
remote start / stop setup.

Note: If ‘YES’ had been selected previously, then ‘YES’ will be
displayed on screen.

Step 3

Press and release DOWN arrow to change setting to ‘YES.’
To change setting back to ‘NO’ press and release UP arrow.

Step 4

After you’ve made your selection, press and release RIGHT
arrow button. This saves your setting.
You can now modify other settings in Mode 0 or you can exit
Setup by pressing and holding SELECT RUN MODE button
for a few seconds until you return to Run screen.

Running pump with Remote Start / Stop enabled, ‘REMOTE’ icon will always be visible on lower left side of screen.
Pump will display ‘STBY’ (standby) if pump is in stop mode via contact closure signal. Please use caution in this mode, pump can
start at anytime. If you must perform maintenance to pump, press and release STOP button.

Mode 0

SEt

0

Mode 0

no

0

Remote

Icon

Mode 0

yes

0

Mode 0

yes

0

REMOTE

REMOTE

REMOTE

7.0

Mode 0 - Set Remote Start / Stop