70 appendix d product specifications, Inputs, Input performance – West Control Solutions MRC 8000 User Manual
Page 70
70
Appendix D Product Specifications
INPUTS
Input Types/Range
Type
Range
Thermocouple
J
0
°
C to 760
°
C
0
°
F to 1400
°
F
K
0
°
C to 1360
°
C
0
°
F to 2500
°
F
T
-200
°
C to 400
°
C
-330
°
F to 750
°
F
R
200
°
C to 1650
°
C
400
°
F to 3000
°
F
S
200
°
C to 1650
°
C
400
°
F to 3000
°
F
E
0
°
C to 750
°
C
0
°
F to 1400
°
F
B
200
°
C to 1800
°
C
400
°
F to 3300
°
F
N
0
°
C to 1300
°
C
0
°
F to 2370
°
F
C
200
°
C to 2300
°
C
390
°
F to 4170
°
F
RTD
100 ohm Platinum
-140
°
C to 400
°
C
-220
°
F to 750
°
F
.00385 ohms/ohm/
°
C
Current DC
0 to 20mA, 4 to 20mA
External Shunt Resistor, 2.5 ohms or 250 ohms
Voltage DC
0 to 25mV, 0 to 50mV, 10 to 50mV, 0 to 5 V, 1 to 5 V
Impedance
> 100M ohm for TC and mV inputs
100K ohms for 5V inputs
2.5 ohms or 250 ohms for mA inputs
RTD Excitation Current
330 microamps, typical
Input Scan Rate
1 scan per second
Input Correction
Offset Adjustment, -999 to 999 units
Remote Setpoint
0 to 5V, 1 to 5V
Sensor Fault Detection
Sensor break on all TCs, RTDs, 1volt, 1 to 5 volt, 4-20mA, and millivolt inputs
No sensor break can be detected for zero based Volt and Milliamp ranges
Display goes to “SnSr” and pen goes upscale if a sensor break is detected
Display goes to “Hi” 5% above span
Display goes “Lo” 5% below span
Transmitter Power Supplies
One isolated 50mA @ 24VDC supply available
.
INPUT PERFORMANCE
Performance Under Reference Condition:
Measurement Error
Type J, K, T, E, N, C, T/C and RTD:
±
0.25% of span
±
1 degree
Type R, S, B, C, T/Cs:
±
0.25% of span @ 25
°
C
mVDC and VDC:
±
0.25% of scaled span plus 1 least significant digit
Cold Junction Compensation Error
±
0.2
°
C @ 25
°
C
Cold Junction Compensation Rejection
0.04
°
/
°
C deviation from 25
°
C
Linearization Error
TCs:
±
0.25
°
C typical,
±
0.5
°
C worst case with expectations
RTDs:
±
0.1
°
C typical,
±
0.3
°
C worst case
Ambient Temperature Error
±
0.01% of span per
°
C deviation from 25
°
C
Common Mode Rejection
90 db minimum; 24VAC maximum for RTD input; 115 VAC maximum all others
for other inputs
Normal Mode Rejection
85 dB minimum @60Hz or greater
Isolation
RTD Inputs 24VAC. All other inputs 115VAC
Inputs share a common signal ground
Reference Conditions
Ambient Temperature
25
°
C
Relative Humidity
60 - 70%
Supply Voltage
115 VAC, 60 Hz
Source Resistance
< 10 ohms for TC input
Lead Resistance
< 0.1 ohm/lead balanced (Pt100)