beautypg.com

2 configuration: 73, Additions othr – West Control Solutions N8800 User Manual

Page 73

background image

7.4 8800 process controller as Modbus master

a

This function is only selectable with 8800/8840 configurator (engineering tool)!

The 8800 process controller can be used as Modbus master ( ConF / othr /

MASt = 1 ). The Modbus master sends ist data to all slaves (Broadcast message,

controller adress 0). It transmits its data (modbus adress AdrU) cyclic with the

cycle time Cycl to the bus. The slave controller receives the data transmitted by

the masters and allocates it to the modbus target adress AdrO. If more than one

data should be transmitted by the master controller ( Numb > 1) , the modbus

adress AdrU indicates the start adress of the data that should be transmitted and

AdrO indicates the first target adress where the received data should be stored.

The following data will be stored at the logically following modbus target

adresses.

With this it is possible e.g. to specify the process value of the master controller as

set-point for the slave controllers.

Special functions

8800 process controller

73 8800 process controller as Modbus master

Additions othr

(only visible with 8800/8840 configurator!)

Name

Value range Description

Default

MASt

Controller is used as Modbus master

0

0

Slave

1

Master

Cycl

0...200

Cycle time [ms] for the Modbus master to transmit its data

to the bus.

60

AdrO

1...65535

Target address to which the with

AdrU

specified data is

given out on the bus.

1

AdrU

1...65535

Modbus address of the data that Modbus master gives to

the bus.

1

Numb

0...100

Number of data that should be transmitted by the Modbus

master.

0