Continuous controller 58 – West Control Solutions N8800 User Manual

Page 58

background image

4.5.7 8800 process controller with measured value output

ConF / Out.3 / 4: O.tYP = 1

Out.3/ 4 0...20mA continuous

= 2

Out.3/ 4 4...20mA continuous

= 3

Out.3/ 4 0...10V continuous

= 4

Out.3/ 4 2...10V continuous

Out.0 = -1999...9999

scaling Out.3/ 4

for 0/4mA or 0/2V

Out.1 = -1999...9999

scaling Out.3/ 4

for 20mA or 10V

O.Src = 3

signal source for Out.3/ 4 is

the process value

Configuration level

Configuration examples

58

8800 process controller