beautypg.com

Out.1 – West Control Solutions N8800 User Manual

Page 37

background image

Configuration level

8800 process controller

37

Configuration parameters

Name

Value range Description

Default

Src.3

Source of limit 3

0

0

process value

1

control deviation xw (process value - set-point)

2

control deviation xw (with suppression after start-up and

set-point change)
After switch-on or set-point changing, the alarm output is

suppressed, until the process value is within the limits for the

first time. At the latest after elapse of time 10 ti1 the alarm

is activated (ti1 = integral time 1; parameter r Cntr)

If ti1 is switched off (ti1 = 0), this is interpreted as Î ,

i.e. the alarm is not activated, before the process value was

within the limits once.

3

measured value INP1

4

measured value INP2

5

measured value INP3

6

effective setpoint Weff

7

correcting variable y (controller output)

8

control variable deviation xw (actual value - internal setpoint)

= deviation alarm to internal setpoint

9

difference x1 - x2 (utilizable e.g. in combination with process

value function “mean value” for recognizing aged

thermocouples

HC.AL

Alarm heat current function (INP2)

0

0

switched off

1

Overload short circuit monitoring

2

Break and short circuit monitoring

LP.AL

Monitoring of control loop interruption for heating

0

0

switched off / inactive

1

active.

If ti1=0 LOOP alarm is inactive!

dAc.A

DAC alarm function

0

0

DAC alarm switched off / inactive

1

DAC alarm active

Hour

OFF...999999

Operating hours (only visible with 8800/8840 configurator!)

OFF

Swit

OFF...999999

Output switching cycles (only visible with 8800/8840

configurator!)

OFF

Out.1

Name

Value range Description

Default

O.Act

Method of operation of output OUT1

0

0

direct / normally open

1

inverse / normally closed

Y.1

Controller output Y1

1

0

not active

1

active